Mr. Bernard P. Orlan November 6, 2001 Indoor Air Quality Assessment Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and eighteen (118) sets of real-time environmental measurements consisting of one hundred and fifteen (116) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:20 A.M. and concluded after 1:15 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69.6 °F to 77.2 °F. Twenty-seven (27) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected in rooms on the 8^^, 6^^, 5th, 4th, 3rd ^nd 2^^ floors. The outdoor temperature range was 52.1 to 54.4 °F.

Relative Humidity

The relative humidity indoors ranged from 20.0 percent to 34.1 percent. Only five (5) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 24.4 and 29.4 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 401 ppm to 1583 ppm. Thirteen (13) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 377 and 373 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1077 ppm (background level + 700 ppm). The highest reading, 1583 ppm, was in Room 525. Rooms with CO2 levels above the recommended maximum were found on the 3’'*^, 4th, 5th and 6^ floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide was not detected anywhere inside the building (0 ppm). The outdoor CO concentration was also 0 ppm.

Respirable Particulates (PM2,§)

Respirable particulate concentrations indoors ranged between 5 pg/m^ and 21 pg/m^. All of the measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 27 and 36 pg/m^.

CITY_21MC100_003081737

NYC-WTC_000293097

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000293097Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000293059

Indoor air quality assessment conducted late Oct–early Nov 2001 at Stuyvesant High School.

Similar indexed content

NYC-WTC_000271280

Memo reporting indoor air quality assessment at Stuyvesant High School, Nov 2001.

Similar indexed content

Compare copies and versions →