NYC-WTC_000293095
Indoor air quality assessment report for Stuyvesant High School conducted for NYC Department of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality assessment conducted late Oct–early Nov 2001 at Stuyvesant High School.
NYC-WTC_000293059–000293063OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orian November 2, 2001 Indoor Air Quality Assessment Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246
Real-Time Environmental Measurements
ATC collected one hundred and fifteen (115) sets of real-time environmental measurements consisting of one hundred and thirteen (113) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in .Attachment 1. Readings began at 9:00 A.M. and concluded after 2:20 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 72.2 °F to 79.3 °F. Seventy-two (72) measurements were above the range of 69 to 76°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected in rooms on all floors. The outdoor temperature range was 61.9 to71.8 °F.
Relative Humidity
The relative humidity indoors ranged from 36.9 percent to 50.2 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements were 38.7 to 44.2 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 438 ppm to 1850 ppm. Eleven (11) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 395 and 400 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1100 ppm (background level + 700 ppm). The highest reading, 1850 ppm, was in Room 303. Rooms with CO2 levels above the recommended maximum were found on the 2’’'^, 3’'*^, 41'1, 5th, 7^11 and 8^^ floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide was not detected anywhere inside the building (0 ppm). The outdoor CO concentration was also 0 ppm.
Respirable Particulates (PM2 S)
Respirable particulate concentrations indoors ranged between 37 pg/m^ and 88 pg/m3. Eighteen (18) of the measurements were above the NPAAQS of 65 pg/ra^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 83 and 107 pg/m^.
CITY_21MC100_006797435
NYC-WTC_000293061
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000293095
Indoor air quality assessment report for Stuyvesant High School conducted for NYC Department of Education.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271213
ATC IAQ assessment report for Stuyvesant High School dated Oct 25, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182684
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 1, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182689
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 2, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292952
ATC IAQ assessment conducted at Stuyvesant High School, Oct 2001, for NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271280
Memo reporting indoor air quality assessment at Stuyvesant High School, Nov 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293103
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292936
Report of an indoor air quality assessment conducted at Stuyvesant High School on Oct 18, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271218
Indoor air quality field report for Stuyvesant High School dated Oct 29, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271233
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000293095
Indoor air quality assessment report for Stuyvesant High School conducted for NYC Department of Education.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271213
ATC IAQ assessment report for Stuyvesant High School dated Oct 25, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182689
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 2, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292982
IAQ assessment conducted at Stuyvesant High School on Oct 23, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255904
Indoor air quality measurements collected January 18, 2002, at Stuyvesant HS.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Indoor air quality assessment report for Stuyvesant High School conducted for NYC Department of Education.
Similar indexed content
NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
Similar indexed content
NYC-WTC_000271213
ATC IAQ assessment report for Stuyvesant High School dated Oct 25, 2001.
Similar indexed content
NYC-WTC_000182684
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 1, 2001.
Similar indexed content
NYC-WTC_000182689
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 2, 2001.
Similar indexed content