Mr. Bernard P. Orlan Februaiy 12, 2002 Indoor Air Quality Assessment Page 3 P. S. 234M ATC Project No. 15-19125-0279

Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of forty-nine (49) from inside the school building and eleven (11) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 10:00 A.M. and concluded after 2:50 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 64.9 °F to 76.1 °F. One (1) measurement was below the range of 68 to 75 °F and one (1) measurement was above (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 34.0 to 39.8 °F.

Relath^HumidJjy

The relative humidity indoors ranged from 25.8 percent to 43.9 percent. Nine (9) of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were within the recommended range. The outdoor relative humidity ranged from 28.0 to 31.8 percent.

Carbon Dioxide Conce/itration

Carbon dioxide concentrations indoors ranged from 599 ppm to 2229 ppm. Twenty-seven (27) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 470 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1170 ppm (background level + 700 ppm). The highest measurement was recorded in room 319. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon MonoxideQtncentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 0 to 2 ppm.

Respirable Particulates (PM2,^)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 18 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 10 pg/m^. This average concentration was below the USEPA recommended concentration for sensitive individuals such

CITY_21MC100_003101679

NYC-WTC_000182881

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000182881Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →