NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 4. 2002
Indoor Air Quality Assessment Page 3
P. S. 234M ATC Project No. 15-19125-0279
Real-Time Environmental Measurements
ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty-two
(52) from inside the school building and eight (8) outdoors. All three floors of the school were
surveyed. These results are described below. Field data sheets are found in Attachment 1.
Readings began at 12:00 P.M. and concluded after 1:50 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 66 °F to 76.8 °F. Seven (7)
measurements were above and one (1) below the range of 68 to 75°F (at 50 percent relative
humidity) as recommended by ASHRAE Standard 55-1992 dunng the heating season
(wintertime conditions). The outdoor temperature measurements ranged from 47.4 to 48.5 °F.
Relative Humidity
The relative humidity indoors ranged from 16.5 percent to 29.2 percent. All of the indoor of the
measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. The outdoor relative humidity ranged from 15.8 to 19.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 686 ppm to 1380 ppm. Five (5) of the
indoor measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 493 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1193 ppm (background level + 700 ppm). The highest measurement was recorded
in Room 322 at 1:50 PM. Levels above the recommended maximum do not indicate a health
risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The
primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were
also 0 ppm.
Respirable Particulates (PM2 ,5)
Respirable particulate concentrations* indoors ranged between 13 pg/ra^ to 30 AU
measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 21 pg/m^. This average
concentration was below the USEPA recommended concentration for sensitive individuals such
as asthmatic people and children. The outdoor respirable particulate concentration ranged from
24 to 34 pg/m3 with an average of 28 pg/m^.
C11Y_21MC100_002811610
NYC-WTC_000217727