NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 4, 2002
Indoor Air Quality Assessment Page 2
P.S.234M ATC Project No. 15-19125-0279
The results of the sampling represent conditions found on the dates of the survey and may not
represent conditions found at other times. The information presented in this report should be
used by the BOE as a guide to assess the need for further improvements in current indoor air
quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings,
such as offices and schools. For the real-time data collected, ATC uses the commonly accepted
guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE);
Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992);
Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American
Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation.
Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality
will be achieved at all times.
TABLE 1
TARGET GUIDELINES FOR LNDOOR AIR QUALITY PARAMETERS EVALUATED
a
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62
(CO2) above background level
Carbon Monoxide 9 ppm ASHRAE 62 (adopted from
(CO)____________ USEPA NPAAQS)
Respirable 65 micrograms per cubic meter USEPA NPAAQS
Particulates (PM2.5) of air (pg/m^) 24-hour average
40 pg/m^ 24-hour average USEPA - recommendation for
children/sensitive individuals
Temperature Summer; 73-79°F at 50% RH ASHRAE 55
Winter: 68-75°F at 50% RH
Relative Humidity 30-60% ASHRAE 55
Total Volatile
Organic Compounds 1 ppm AIHA
(TVOC)
USEPA = United States Environmental Protection Agency
NPAAQS = National Primary Ambient-Air Quality Standard
AIHA = American Industrial Hygiene Association
CITY_21MC100_002877609
NYC-WTC_000217726
OCR can misread numbers and units. Confirm readings against the page image before using them.