NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 4, 2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Protect No. 15-19125-0279
* The measurements made during this assessment were instantaneous readings, the NKYAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following;
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
Mil[NGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were below the applicable standards and guidelines.
2. None of the PM2.5 measurements were above the NPAAQS of 65 pg/m^ or above the
USEPA recommended PM2 5 concentration of 40 pg/m^ for sensitive individuals and
children.
3. All measurements of the relative humidity were below the ASHRAE recommended range of
30 to 60 percent for occupant comfort.
4. Seven (7) of the temperature measurements were above and one (1) was below the range of
68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992
during thp heating season (wintertime conditions).
5. Five (5) CO2 indoor measurements were above the range recommended by ASHRAE 62-
1999.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
336 or 212.
Sincerely,
/I TC ASSOCIA TES INC.
Reviewed by:
-—r
Amel J^al James R. Cohn, CM, CSP
Senior Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_002877611
NYC-WTC_000217728
OCR can misread numbers and units. Confirm readings against the page image before using them.