NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 7, 2002
Indoor Air Quality Assessment Page 4
P. S. 234M ATC Project No. 15-19125-0279
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• The building was occupied at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO ,CO2and TVOCs were within applicable standards and guidelines.
2. None of the PM2.5 measurements were above the NPAAQS of 65 pg/m3 or above the
USEPA recommended PM2.5 concentration of 40 pg/m^ for sensitive individuals and
children.
3. All of the measurements of relative humidity were below the ASHRAE recommended range
of 30 to 60 percent for occupant comfort.
4. Eighteen (18) of the temperature measurements were above the range of 68 to 75°F (at 50
percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the
heating season (wintertime conditions).
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
211 or 212.
Sincerely,
A TC ASSOCIA TES INC.
Reviewed by:
Yiannis Efsta tou James R. Cohn, CIH, CSP
Project Manager Regional Manager, Industrial Hygiene Division
Attachment
CITY_21MC100_003032134
NYC-WTC_000199186