NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 5 pages

Indoor air quality, Stuyvesant H.S., Dec 2001

Machine-extracted title · confidence 40%

Indoor air quality report for Stuyvesant High School, Dec 4, 2001.

NYC-WTC_000273872–000273876
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

f

Mr. Bernard P. Orlan December 4, 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School (M477) ATC Project No. 15-19125-0246

ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 7:45 A.M. and concluded after 3:45 P.M.

Temperatiirs

Indoor dry bulb temperature measurements ranged from 71.1 °F to 80.0 °F. Fifty-eight (58) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 57.9 to 69.5 °F.

Relative Humidity

The relative humidity indoors ranged from 25.3 percent to 37.2 percent. Seventy (70) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 26.2 and 37.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 580 ppm to 2049 ppm. Eight (8) COg measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 540 ppm and 560 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1260 ppm (background level -I- 700 ppm). The highest reading, 2049 ppm, was in Room 715. Rooms with CO? levels above the recommended maximum were found on the 3rd, 4th, 5th. 7th and floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration.

Carb on Monoxide Concentration

Carbon monoxide concentrations indoors were 1-2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 2 ppm.

Respirable Particulates (PM2,5.)

Respirable particulate concentrations* indoors ranged between 30 gg/m^ to 94 pg/m^. Thirty (30) measurement were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 110 and 1 13 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3‘'d, 4th, 6th and 7th floors (See Attachment 1). The PM?.5 concentration range for those rooms was 41 - 81 pg/m^ with an average of 63 pg/m-’. The PM2 5 concentration range for the other rooms was 30 - 94 pg/m^ with an average of approximately 55 pg/m^. The average PM?.5 concentration for the entire school building was approximately 57 pg/m^. Ln addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA)

CnY_21MC10 0_0 03106816

NYC-WTC_000273874

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000273874Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255452

Indoor air quality measurements at Stuyvesant High School, December 4, 2001.

Similar indexed content

Compare copies and versions →