Mr. Bernard P. Orlan December 5, 2001 Indoor Air Quality Assessment Page 3 Stuyvesant High School (M4771 ATC Project No. 15-19125-0246
ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:10 A.M. and concluded after 4.T0 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 71.4 °F to 77.5 °F. Fifty-four (54) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 60.0 to 71.5 °F.
Relative Humidity
The relative humidity indoors ranged from 27.7 percent to 41.8 percent. Twenty-three (23) measurements were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 29.1 and 36.0 percent.
Carbon Dioxide Concentralion
Carbon dioxide concentrations indoors ranged from 565 ppm to 2015 ppm. Nine (9) COp measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 501 ppm and 536 ppm. Therefore, the maximum acceptable level of COn at this location was 1236 ppm (background level + 700 ppm). The highest reading, 2015 ppm, was in Room 738. Rooms with CO2 levels above the recommended maximum were found on the 1st, 3rd, 4th, gth, 7th and Sth floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentralion
Carbon monoxide concentrations indoors were 1-2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 - 2 ppm.
Respirable Particulates ('PM2,5}
Respirable particulate concentrations* indoors ranged between 27 pig/m^ to 80 gg/m^. One (I) measurement was above the NPAAQS of 65 gg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 53 and 85 gg/m^.
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, 6th and 7th floors (See Attachment 1). The PM2 5 concentration range for those rooms was 27 - 54 ug/m^ with an average of 41 gg/m^. The PM2.5 concentration range for the other rooms was 27 - 80 pig/m^ with an average of approximately 47 pig/m^. The average PM2.5 concentration for the entire school building was approximately 46 fig/nP. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA)
CITY_21MC100_003106896
NYC-WTC_000273892
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255452
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293103
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292936
Report of an indoor air quality assessment conducted at Stuyvesant High School on Oct 18, 2001.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292952
ATC IAQ assessment conducted at Stuyvesant High School, Oct 2001, for NYC Board of Education.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255939
February 2002 IAQ measurements at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271218
Indoor air quality field report for Stuyvesant High School dated Oct 29, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311313
ATC report of IAQ measurements at Stuyvesant High School (M477).
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000407007
ATC IAQ report to NYC Board of Education for Stuyvesant High School, June 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000255452
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401584
Indoor air quality measurements summary for December 24, 2001 at Stuyvesant High School.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311627
Correspondence and IAQ measurements report for Stuyvesant High School dated February 18, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
Similar indexed content
NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
Similar indexed content
NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
Similar indexed content
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
Similar indexed content
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
Similar indexed content