Mr. Bernard P. Orlan December 3, 2001 Indoor Air Quality Assessment Page 3 Stuvvesant High School (M477) ATC Project No. 15-19125-0246
ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 7:45 A.M. and concluded after 4:02 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 67.9 °F to 76.9 °F. Two (2) measurements were above and one (1) measurement was below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 49.6 to 64.9 °F.
Rc/a(ive Humidity
The relative humidity indoors ranged from 29.4 percent to 43.0 percent. Three (3) measurements were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 29.8 and 39.1 percent.
Carbon Dioxide Concentralion
Carbon dioxide concentrations indoors ranged from 570 ppm to 1530 ppm. Twelve (12) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 545 ppm and 570 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1270 ppm (background level + 700 ppm). The highest reading, 1530 ppm, was in Room 735. Rooms with CO2 levels above the recommended maximum were found on the 3''^, 4tli, 5th, 7th and 91'1 floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1-3 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 - 2 ppm.
Respirable Particulates (PM2,5)
Respirable particulate concentrations* indoors ranged between 20 pg/m^ to 90 pg/nP. Nineteen (19) measurement were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 70 and 120 pg/m^.
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3''d, 4th, 6’'' and 7^^ floors (See Attachment 1). The PM2.5 concentration range for those rooms was 20 - 60 pg/m3 with an average of 40 pg/inT The PM2.5 concentration range for the other rooms was 21-90 pg/m^ with an average of approximately 54 pg/m-’. The average PM2.5 concentration for the entire school building was approximately 44 pg/m^. In addition to higher efficiency rating fdters on their HVAC units, portable High Efficiency Particulate Air (HEPA)
CITY_21MC100_003106856
NYC-WTC_000273856
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292936
Report of an indoor air quality assessment conducted at Stuyvesant High School on Oct 18, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255452
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271233
Indoor air quality field report for Stuyvesant High School dated Oct 30, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273926
IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271218
Indoor air quality field report for Stuyvesant High School dated Oct 29, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255772
Indoor air quality measurements collected Jan 31, 2002 at Stuyvesant.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255452
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255501
Indoor air quality measurements collected at Stuyvesant High School on December 7, 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311819
ATC IAQ assessment report issued for Stuyvesant High School.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273926
IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
Similar indexed content
NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
Similar indexed content
NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
Similar indexed content
NYC-WTC_000292936
Report of an indoor air quality assessment conducted at Stuyvesant High School on Oct 18, 2001.
Similar indexed content
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
Similar indexed content