Mr. Bernard P. Orlan December 7, 2001 Indoor Air Quality Assessment Page 3 StLivvesant High School (M477) ATC Project No. 15-19125-0246
data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 3:55 P.M. ■
Temperature
Indoor dry bulb temperature measurements ranged from 72.2 °F to 79.4 °F. Seventy-eight (78) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 58.6 to 71.3 °F.
Relative Humidity
The relative humidity indoors ranged from 35.5 percent to 52.0 percent. All measurements were within the ASHRAE-recomtnended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 35.0 and 48.0 percent.
Carbon Dioxide Cejnceniraiion
Carbon dioxide concentrations indoors ranged from 539 ppm to 1558 ppm. Ten (10) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 469 ppm and 478 ppm. Therefore, the maximum acceptable level of CO2 at this location was 11 78 ppm (background level -I- 700 ppm). The highest reading, 1 558 ppm, was in Room 735. Rooms with CO2 levels above the recommended maximum were found on all floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 52 pg/m^. All measurements were below the NPAAQS of 65 pg/m3 24.-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 4 and 63 pg/m^.
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3'*^, 4^11, 6’^^’ and 7th floors (See Attachment 1). The PM2.5 concentration range for those rooms was 20 - 52 gg/m^ with an average of 38 pg/m^. The PM2.5 concentration range for the other rooms was 15-52 pg/m^ with an average of approximately 28 pg/m^. The average PM2.5 concentration for the entire school building was approximately 30 pg/mA In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA).
CONFIDENTIAL, CITY_21MC100_003457106 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000255503
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000273926
IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274049
December 21, 2001 IAQ measurements at Stuyvesant High School for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000336454
Indoor air quality measurements at Stuyvesant HS; March 18, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401672
ATC memo documenting IAQ measurements taken January 25, 2002 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311384
ATC memo reporting IAQ measurements at Stuyvesant High School, Jan 25, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401584
Indoor air quality measurements summary for December 24, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406576
April 16, 2002 memo documenting IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255612
ATC report of IAQ measurements at Stuyvesant High School for December 2001.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000204475
ATC Associates memo reporting indoor air quality measurements collected at a New York City Board of Education school in April 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311555
ATC IAQ measurements report for Stuyvesant High School, Feb 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273926
IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311819
ATC IAQ assessment report issued for Stuyvesant High School.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255452
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255939
February 2002 IAQ measurements at Stuyvesant High School.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.
Similar indexed content
December 21, 2001 IAQ measurements at Stuyvesant High School for BOE.
Similar indexed content
Indoor air quality measurements at Stuyvesant HS; March 18, 2002.
Similar indexed content
ATC memo documenting IAQ measurements taken January 25, 2002 at Stuyvesant High School.
Similar indexed content
ATC memo reporting IAQ measurements at Stuyvesant High School, Jan 25, 2002.
Similar indexed content