IAQ memo, Stuyvesant High School, Feb 2002

Machine-extracted title · confidence 52%

February 2002 IAQ measurements at Stuyvesant High School.

NYC-WTC_000255939–000255943
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 4, 2002 Indoor Air Quality Measurements Page 3 Stuvvesant High School (M477) ATC Proiect No. 15-19125-0246

Real-Time Eiyvironmental Measurements

ATC collected one hundred and twenty-one (121) sets of real-time environmental measurements consisting of one hundred and nineteen (119) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 1:50 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69.9°F to 74.8°F. All of the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions)'. The outdoor temperature range was 41.9 to 49.3 °F.

Relative Humidity

The relative humidity indoors ranged from 27.6 percent to 31.9 percent. Twenty-eight (28) of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 30.0 and 47.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 459 ppm to 1236 ppm. None of the CO2 measurements were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 553 and 560 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1260 ppm (background level + 700 ppm). The highest reading, 1260 ppm, was in Room 804. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 0 - Ippm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 25 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 33 and 36 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, 6th and 7th floors (See Attachment 1). The PM2.5 concentration range for those rooms

CONFIDENTIAL, CITY_21MC100_003457718 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255941

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255941Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255739

Indoor air quality measurements collected January 29–31, 2002 at Stuyvesant.

Similar indexed content

NYC-WTC_000311333

ATC report of IAQ measurements collected at Stuyvesant High School.

Similar indexed content

NYC-WTC_000311421

ATC memo reporting indoor air quality measurements at Stuyvesant High School.

Similar indexed content

NYC-WTC_000336131

May 20, 2002 IAQ measurements at Stuyvesant High School for BOE.

Similar indexed content

Compare copies and versions →