Indoor air quality report, Stuyvesant H.S., Dec 2001

Machine-extracted title · confidence 33%

Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.

NYC-WTC_000273908–000273912
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlaii December 6, 2001 Indoor Air Quality Assessment Page 3 Stuyvesant High School (MA??) ATC Project No. 15-19125-0246

data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 3:50 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 71.9 °F to 80.0 °F. Eighty-two (82) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 62.3 to 70.7 °F.

Relative Humidity

The relative humidity indoors ranged from 29.1 percent to 41.0 percent. Only one (1) measurement, in room 411, was below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 30.0 and 34.8 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 561 ppm to 1699 ppm. Eleven (11) CO2 measurements were above the ASHR.AE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 481 ppm and 490 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1190 ppm (background level + 700 ppm). The highest reading, 2015 ppm, was in Room 738. Rooms with CO2 levels above the recommended maximum were found on all floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/.A.SHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm.

Respirable Particulates CPM2,5)

Respirable particulate concentrations* indoors ranged between 27 p-g/m^ to 70 pg/m^. Two (2) measurement was above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 47 and 58 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3>’d, 4th, 6^*'* and 7^^ floors (See Attachment 1). The PM2.5 concentration range for those rooms was 30 - 59 pg/m^ with an average of 43 pg/m^. The PM2.5 concentration range for the other rooms was 27 - 70 pg/m^ with an average of approximately 50 pg/m^. The average PM2.5 concentration for the entire school building was approximately 49 pg/m^. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA)

CITY_21MC100_003106916

NYC-WTC_000273910

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000273910Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255452

Indoor air quality measurements at Stuyvesant High School, December 4, 2001.

Similar indexed content

NYC-WTC_000273926

IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.

Similar indexed content

Compare copies and versions →