Mr. Bernard P. Orlaii December 6, 2001 Indoor Air Quality Assessment Page 3 Stuyvesant High School (MA??) ATC Project No. 15-19125-0246
data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 3:50 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 71.9 °F to 80.0 °F. Eighty-two (82) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 62.3 to 70.7 °F.
Relative Humidity
The relative humidity indoors ranged from 29.1 percent to 41.0 percent. Only one (1) measurement, in room 411, was below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 30.0 and 34.8 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 561 ppm to 1699 ppm. Eleven (11) CO2 measurements were above the ASHR.AE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 481 ppm and 490 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1190 ppm (background level + 700 ppm). The highest reading, 2015 ppm, was in Room 738. Rooms with CO2 levels above the recommended maximum were found on all floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 ppm for all readings. These concentrations were below the NPAAQS/.A.SHRAE guideline of 9 ppm. The outdoor CO concentration was also 1 ppm.
Respirable Particulates CPM2,5)
Respirable particulate concentrations* indoors ranged between 27 p-g/m^ to 70 pg/m^. Two (2) measurement was above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 47 and 58 pg/m^.
Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3>’d, 4th, 6^*'* and 7^^ floors (See Attachment 1). The PM2.5 concentration range for those rooms was 30 - 59 pg/m^ with an average of 43 pg/m^. The PM2.5 concentration range for the other rooms was 27 - 70 pg/m^ with an average of approximately 50 pg/m^. The average PM2.5 concentration for the entire school building was approximately 49 pg/m^. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA)
CITY_21MC100_003106916
NYC-WTC_000273910
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255452
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273926
IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292936
Report of an indoor air quality assessment conducted at Stuyvesant High School on Oct 18, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293103
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292952
ATC IAQ assessment conducted at Stuyvesant High School, Oct 2001, for NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255939
February 2002 IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311313
ATC report of IAQ measurements at Stuyvesant High School (M477).
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311333
ATC report of IAQ measurements collected at Stuyvesant High School.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255452
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401584
Indoor air quality measurements summary for December 24, 2001 at Stuyvesant High School.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273926
IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406539
April 11, 2002 memo documenting IAQ measurements at Stuyvesant High School.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
Similar indexed content
NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
Similar indexed content
NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
Similar indexed content
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
Similar indexed content
IAQ measurements conducted December 2001 at Stuyvesant High School for environmental health.
Similar indexed content