Mr. Bernard P. Orlan April 11,2002 Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246

Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 12:50 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 64.8°F to 74.5°F. One (1) of the measurements was below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 49.8 to 50.2°F.

Relative Humidity

The relative humidity indoors ranged from 29.7 percent to 45.8 percent. One (1) measurement was below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort.. The outdoor relative humidity levels were 49.8 and 52.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 384 ppm to 1014 ppm. All of the CO2 measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 376 and 398 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1098 ppm (background level ■+• 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 2 ppm.

Respirable Particulates (PM2^s)

Respirable particulate concentrations* indoors ranged between 9 pg/m^ to 19 pg/m^ with an average of approximately 14 pg/m\ None of the measurements were above the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 26 and 28 pg/m^.

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 7-18 pg/m^ with an average of approximately 14 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_002902699

NYC-WTC_000406541

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000406541Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000336177

Indoor air quality measurements collected April 11, 2002 for Stuyvesant High School.

Similar indexed content

NYC-WTC_000311502

ATC IAQ measurements report for Stuyvesant High School, Feb 2002.

Similar indexed content

Compare copies and versions →