Indoor air quality report, Stuyvesant H.S., Dec 2001

Machine-extracted title · confidence 34%

IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.

NYC-WTC_000273890–000273894
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan December 5, 2001 Indoor Air Quality Assessment Page 4 StLiyvesant High School (M477) ATC Project No. 15-19125-0246

purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 27 - 54 pg/nO with an average of approximately 41 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the buildmg appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The portable HEPA air purifier in room 638 was shut off; • Respirable particulates concentration of 80 pg/m^ was detected in the wood shop 350. Students were cutting wood at the time of ATC’s assessment.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were within applicable standards and guidelines.

2. Nine (9) CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Fifty-four (54) temperature measurements were above the range recommended by ASHRAE 55-1992.

4. One (1) measurement of respirable particulates was above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The measurements made during this assessment were instantaneous readings.

5. Twenty-three (23) measurements of relative humidity were below the range recommended by ASHRAE33.

CITY_21MC1OO_OO31O6897

NYC-WTC_000273893

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000273893Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255452

Indoor air quality measurements at Stuyvesant High School, December 4, 2001.

Similar indexed content

NYC-WTC_000293103

Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.

Similar indexed content

Compare copies and versions →