Mr. Bernard P. Orlaii December 4. 2001 Indoor Air Quality Assessment Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246
purifiers were placed in Rooms 327, 333, 638 and 740. The PMg.p concentration range for these rooms w'as 40 - 64 pg/m-’ with an average of approximately 50 pg/m-’.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Concentration
TVOCs were not detected anywhere inside the building (0.0 ppm) except in room 727 where a TVOCs concentration of 7 ppm was detected. The outdoor TVOC concentration was 0-0.1 ppm.
OBSERVATION
During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The portable HEPA air purifier in room 6.38 was shut off; • TVOCs concentration of 7 ppm w'as detected in laboratory room 727. At that time, students were cleaning microscope lenses with alcohol which contribute in the detection of TVOCs.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were within applicable standards and guidelines. TVOCs concentration of 7 ppm was detected in laboratory room 727 where students were cleaning microscope lenses with alcohol.
2. Eight (8) COg measurements were above the range recommended by ASHRAE 62-1999. Ail others w'ere below the recommended maximum concentration.
3. Fifty-eight (58) temperature measurements were above the range recommended by ASHRAE 55-1992.
4. Thirty (30) measurement of respirable particulates was above the NPAAQS of 65 pg/m^ 24- hoLir average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The measurements made during this assessment were instantaneous readings.
5. Seventy (70) measurements of relative humidity were below the range recommended by ASHRAE 55.
CITY_21MC100_003106877
NYC-WTC_000273875
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255452
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292952
ATC IAQ assessment conducted at Stuyvesant High School, Oct 2001, for NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293059
Indoor air quality assessment conducted late Oct–early Nov 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293103
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292936
Report of an indoor air quality assessment conducted at Stuyvesant High School on Oct 18, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406788
Indoor air quality measurements at Stuyvesant High School conducted May 17, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255939
February 2002 IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406805
May 20, 2002 report of indoor air quality measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000255470
Indoor air quality measurements conducted at Stuyvesant High School in December 2001.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311333
ATC report of IAQ measurements collected at Stuyvesant High School.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000229474
Report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on April 23, 2002.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311313
ATC report of IAQ measurements at Stuyvesant High School (M477).
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
Similar indexed content
NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
Similar indexed content
NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
Similar indexed content
Indoor air quality measurements at Stuyvesant High School, December 4, 2001.
Similar indexed content
NYC-WTC_000292952
ATC IAQ assessment conducted at Stuyvesant High School, Oct 2001, for NYC Board of Education.
Similar indexed content