Mr. Bernard P. Orlaii December 4. 2001 Indoor Air Quality Assessment Page 4 Stuyvesant High School (M477) ATC Project No. 15-19125-0246

purifiers were placed in Rooms 327, 333, 638 and 740. The PMg.p concentration range for these rooms w'as 40 - 64 pg/m-’ with an average of approximately 50 pg/m-’.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm) except in room 727 where a TVOCs concentration of 7 ppm was detected. The outdoor TVOC concentration was 0-0.1 ppm.

OBSERVATION

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The portable HEPA air purifier in room 6.38 was shut off; • TVOCs concentration of 7 ppm w'as detected in laboratory room 727. At that time, students were cleaning microscope lenses with alcohol which contribute in the detection of TVOCs.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were within applicable standards and guidelines. TVOCs concentration of 7 ppm was detected in laboratory room 727 where students were cleaning microscope lenses with alcohol.

2. Eight (8) COg measurements were above the range recommended by ASHRAE 62-1999. Ail others w'ere below the recommended maximum concentration.

3. Fifty-eight (58) temperature measurements were above the range recommended by ASHRAE 55-1992.

4. Thirty (30) measurement of respirable particulates was above the NPAAQS of 65 pg/m^ 24- hoLir average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The measurements made during this assessment were instantaneous readings.

5. Seventy (70) measurements of relative humidity were below the range recommended by ASHRAE 55.

CITY_21MC100_003106877

NYC-WTC_000273875

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000273875Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255452

Indoor air quality measurements at Stuyvesant High School, December 4, 2001.

Similar indexed content

Compare copies and versions →