Mr. Bernard P. Orlan December 5, 2001 Indoor Air Quality Assessment Page 4 Stuyvesant High School (M477) ATCProiectNoJ5-1912520246

purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 27 - 54 pg/m^ with an average of approximately 41 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following; • The interior of the buildmg appeared clean and free of dustand debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The portable HEPA air purifier in room 638 was shut off; • Respirable particulates concentration of 80 |J.g/m'3 was detected in the wood shop 350. Students were cutting wood at the time of ATC’s assessment.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were within applicable standards and guidelines.

2. Nine (9) CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Fifty-four (54) temperature measurements were above the range recommended by ASHRAE 55-1992.

4. One (1) measurement of respirable particulates was above the NPAAQS of 65 jug/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The measurements made during this assessment were instantaneous readings.

5. Twenty-three (23) measurements of relative humidity were below the range recommended by ASHRAE 55.

CONFIDENTIAL, CITY_21MC1OO_OO3457O67 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255473

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255473Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255452

Indoor air quality measurements at Stuyvesant High School, December 4, 2001.

Similar indexed content

Compare copies and versions →