Mr. Bernard P. Orlan December 5, 2001 Indoor Air Quality Assessment Page 3 Stii\'vesant High School (M477) ATC Project No. 15-19125-0246

ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:10 A.M. and concluded after 4:10 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 71.4 °F to 77.5 °F. Fifty-four (54) measurements were above the range of 68 to 75°F (at 50 percent' relative humidity) recommended by ASHRAE Standard 55-1992 during tlie heating season (wintertime conditions). . These measurements were collected throughout the school building. The outdoor temperature range was 60.0 to 71.5 °F.

Relative Humidity

The relative humidity indoors ranged from 27.7 percent to 41.8 percent. Twenty-three (23) measurements were above the ASHRAE-recomm ended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 29.1 and 36.0 percent.-

Carbon Dioxide Conceniraiion

Carbon dioxide concentrations indoors ranged from 565 ppm to 2015 ppm. Nine (9) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 501 ppm and 536 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1236 ppm (background level + 700 ppm). The highest reading, 2015 ppm, was in Room 738. Rooms with CO2 levels above the recommended maximum were found on the ist, 4^11, btlT 7th and 8^11 floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1-2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 1 - 2 ppm.

Respirable Particulates (PMj^)

Respirable particulate concentrations* indoors ranged between 27 pg/m^ to 80 pg/m^. One (1) measurement was above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 53 and 85 pg/m^. ~

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, gth and 7^h floors (See Attachment 1). The PM2.5 concentration range for those rooms was 27 - 54 pg/m^ with an average of 41 pg/m^. The PM2.5 concentration range for the other rooms was 27 - 80 pg/m^ with an average of approximately 47 pg/m^. The average PM2.5 concentration for the entire school building was approximately 46 pg/m^. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA)

CONFIDENTIAL, CITY_21MC100_003457066 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255472

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255472Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255452

Indoor air quality measurements at Stuyvesant High School, December 4, 2001.

Similar indexed content

Compare copies and versions →