Mr. Bernard P. Orlan November 29. 2001 Indoor Air Quality Assessment Page 4 Sttivvesant Hish School (M477) ATC Project No. 15-19125-0246

(HEP.A) purifiers were placed in Rooms 327, 333, 638 and 740. The PMt 5 concentration range for these rooms was 10-32 pg/m^ with an average of approximately 20 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVQC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Measurements of relative humidity and concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Five CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Eighteen (18) temperature measurements were above the range recommended by ASHRAE 55-1992.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or 212.

Sincerely, ATC ASS OCIA TES INC. Reviewed by;

tr An^as C. Andreou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachments

CITY_21MC100_003046175

NYC-WTC_000312286

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000312286Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000312227

Letter transmitting indoor air quality measurements for Stuyvesant High School.

Similar indexed content

NYC-WTC_000402182

March 12, 2002 IAQ measurements report for Stuyvesant High School.

Similar indexed content

Compare copies and versions →