Mr. Bernard P. Orlan December 4, 2001 Indoor Air Quality Assessment Page 4 Stuvvesant Hish School (M477) ATC Project No. 15-19125-0246
purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 40 - 64 pg/m^ with an average of approximately 50 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
TVOC Conceniratioi'i
TVOCs were not detected anywhere inside the building (0.0 ppm) except in room 727 where a TVOCs concentration of 7 ppm was detected. The outdoor TVOC concentration was 0-0.1 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • The interior of the buildijig appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The portable HEPA air purifier in room 638 was'shut off; • TVOCs concentration of 7 ppm was detected in laboratory room 727. At that time, students were cleaning microscope lenses with alcohol which contribute in the detection of TVOCs.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOCs were within applicable standards and guidelines. TVOCs concentration of 7 ppm was detected in laboratory room 727 where students were cleaning microscope lenses with alcohol.
2. Eight (8) CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.
3. Fifty-eight (58) temperature measurements were above the range recommended by ASHRAE 55-1992.
4. Thirty (30) measurement of respirable particulates was above the NPAAQS of 65 pg/m^ 24- hoLir average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The measurements made during this assessment were instantaneous readings.
5. Seventy (70) measurements of relative humidity were below the range recommended by ASHRAE 55.
CONFIDENTIAL, CITY_21MC100_003457047 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000255455
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000293103
Indoor air quality assessment conducted for Stuyvesant High School by ATC Associates.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000271119
October 2001 IAQ assessment report for Stuyvesant High School.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255939
February 2002 IAQ measurements at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311449
ATC memo documenting IAQ measurements collected Jan 31, 2002 at Stuyvesant HS.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000182704
Cover letter from ATC Associates submitting an indoor air quality assessment report for Stuyvesant High School conducted on November 8, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000330258
November 15, 2001 IAQ assessment report to NYC Board of Education.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311313
ATC report of IAQ measurements at Stuyvesant High School (M477).
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
Similarity score 0.990 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000312283
Letter reporting lAQ measurements at Stuyvesant High School.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255434
Indoor air quality measurements report for Stuyvesant HS, Dec 2001.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000406604
April 23, 2002 memo describing IAQ measurements at Stuyvesant High School.
Similarity score 0.988 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000273890
IAQ measurements collected at Stuyvesant High School; Dec 5, 2001.
Similar indexed content
NYC-WTC_000273872
Indoor air quality report for Stuyvesant High School, Dec 4, 2001.
Similar indexed content
NYC-WTC_000273908
Indoor air quality measurements collected on Dec 6, 2001 at Stuyvesant High School.
Similar indexed content
NYC-WTC_000273854
AQI indoor air quality report for Stuyvesant High School, Dec 3, 2001.
Similar indexed content
NYC-WTC_000293037
IAQ assessment conducted at Stuyvesant High School on Oct 30, 2001.
Similar indexed content