NYC Law Department release
Independent mirror · updated as the City releases more · v1.3.3
☕ Buy me a coffee
← Document results/7DCAS/7 World Trade Center, Manhattan Freedom of Information Request
Document / 10 pages

7 World Trade Center legal correspondence, Apr 2002

Machine-extracted title · confidence 65%

Letter from law firm to City regarding administrative matter related to 7 World Trade Center.

NYC-WTC_000173529–000173538

Folder label: “7 World Trade Center, Manhattan Freedom of Information Request”

Page image
Scanned page image, NYC-WTC_000173533
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

r.ioM xo'Ci

April 20 199S

Mayor^s Office of Emergency Mauxgemeat 7 World Trade Center IMsahatfcta Project #96-1346 Review pf Ftotd PUns Archltectnraj Issues

DRAWING COMMENT

A-EG-23 - Maximum travel distance 300 ft Could 2^ c? ress from PIU be through the elevator lobby? It would require change i i doors.

A-M - How the P.O. tank can be rigged into place? - There is no room around tank for piping conn inspections, etc. - How can light fixtures be reached for mainter ance?

A-7-1 - Is it permitted lo open the double doors into ti if: exit corridor? - Detail of door and curb at mechanical rooms. - Correspondence between door # and door typ:. (general). - Are we having any heating or A/C at these rooins? - If type 2 partition is for mechanical rooms (2; u:.), why do we have type 3 here?

A-23-1 - Mechanical rooms should have type 2 partitio- is (sec dwg. D-0). Why do wc have 4 hr. rated ones? • Why do wc have a base under file cabinets? (I detail 15/D-9). - Why do wc have so ioiaiiy partitions type 2 in jthertfaan mechanical rooms? This is a fully spiinklera. floor. - Why not every wall at room 23-10 is sound at cl EMI resistant? Type 12. - Why not every wall al Mayor’s Conference ro )ni is bullet resistant? - Lounge and repro rooms should have type IA partition. - Il was reqfuestcd some kind of wall Treatment f ;•T the long corridor at North side. - Is the pre-action equipment in an enclosed roo n?

NYC-WTC_000173533

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000173533Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000168718 · Box FDNY

Document outlining fire evacuation procedures and objectives for 7 World Trade Center.

Cited alongside this record in an Ask answer

NYC-WTC_000169709 · Box 7DCAS

Formal letter from law firm requesting documents regarding 7 World Trade Center from NYC Department.

Cited alongside this record in an Ask answer

NYC-WTC_000136542

Archival folder label from the Office of the Mayor for World Trade Center records, identified as Folder 0139.

Cited alongside this record in an Ask answer

Compare copies and versions →