← Document results/7DCAS/Mayor's Office of Emergency Management 7 World Trade Center 7th & 23rd floors®New York, New York ®Project # 96-1346
Document / 4 pages

DCAS letter requesting plan revisions, 7 WTC, April 1998

Machine-extracted title · confidence 95%

Letter from DCAS reviewing Final Plans for the Mayor's Office of Emergency Management renovation and requesting consultant revisions.

NYC-WTC_000167813–000167816

Folder label: “Mayor's Office of Emergency Management 7 World Trade Center 7th & 23rd floors®New York, New York ®Project # 96-1346

Page image
Scanned page image, NYC-WTC_000167814
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

April 20, 1998

Mayor’s Office of Emergency Management 7 World Trade Center Manhattan Project #96-1346 Review of Final Plans Architectural Issues

DRAWING COMMENT

A-EG-23 - Maximum travel distance 300 ft. Could 2”“* egress from PIU be through the elevator lobby? It would require change in doors.

A-1-1 - How the P.O. tank can be rigged into place? - There is no room around tank for piping coimection, inspections, etc. - How can light fixtures be reached for maintenance?

A-7-1 - Is it permitted to open the double doors into the exit corridor? - Detail of door and curb at mechanical rooms. - Correspondence between door # and door type, (general). - Are we having any heating or A/C at these rooms? - If type 2 partition is for mechanical rooms (2 hr.), why do we have type 3 here?

A-23-1 - Mechanical rooms should have type 2 partitions (see dwg. D-0). Why do we have 4 hr. rated ones? - Why do we have a base under file cabinets? (Detail 15/D-9). - Why do we have so many partitions type 2 in other than mechanical rooms? This is a fully sprinklered floor. - Why not every wall at room 23-10 is sound and EMI resistant? Type 12. - Why not every wall at Mayor’s Conference room is bullet resistant? - Lounge and repro rooms should have type 1A partition. - It was requested some kind of wall treatment for the long corridor at North side. - Is the pre-action equipment in an enclosed room?

NYC-WTC_000167814

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000167814Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000169713 · Box 7DCAS

Technical review notes on final construction plans for 7 World Trade Center addressing travel distances and mechanical room details.

Similar indexed content

Compare copies and versions →