r.K)M

April 20 99S

Mayor’* OfSce of Emergency Minagemeat 7 WorW Trade Center Majxhaftaa Project #96-1346 Reyien of Finid Plan* Architeotarai Issues

DRAWING COMMENT

A-EG-23 - Maximum travel distance 300 ft. Could 2^ cj ress from PIU be through the elevator lobby? It would require change i 1 doors.

A-1-1 - How the P.O. tank can be rigged into plaoo? - There is no room around tank for piping conn JOtion, inspections, etc. - How can light fixtures be reached for maimer ance?

A-7.1 - Is it penuitted to open the double doors into tl us exit corridor? - Detail of door and curb at mechanical rooms. - Correspondence between door // and door typ(general). - Are we having any heating or A/C at these nxw? - If type 2 partition is for mechanical rooms (2' ir.), why do we have type 3 here?

A.23.I - Mechanical rooms should have type 2 parcitio' is (see dwg. D-0). Why do wc have 4 hr. rated ones? • Why do wc have a base under file cabinets? (I >etail 15/D-9). - Why do wc have so many partitions type 2 in Xhcrtfaan mechanical rooms? This is a fully sprinklcro;. floor. - Why not every wall at room 23-10 is sound ar d EMI resistant? Type 12. - Why not every wall al Mayor’s Conference ro xn is bullet resistant? - Lounge and repro rooms should have type IA partition. • It was requested some kind of wall Treatment f ar the long corridor at North side. - Is the pre-action equipment in an enclosed roo fl?

NYC-WTC_000168709

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000168709Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000169713 · Box 7DCAS

Technical review notes on final construction plans for 7 World Trade Center addressing travel distances and mechanical room details.

Similar indexed content

Compare copies and versions →