← Document results/7DCAS/GENERATOR PREPURCHASE SPECIFICATION
Document / 52 pages

Transmittal of generator prepurchase specifications, March 1998

Machine-extracted title · confidence 90%

Cover sheet transmitting requested prepurchase specifications for generators to the Department of Citywide Administrative Services.

NYC-WTC_000166874–000166925

Folder label: “GENERATOR PREPURCHASE SPECIFICATION

Page image
Scanned page image, NYC-WTC_000166901
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

PPS-Generators

7. Controls shall be included in the switchgear for the automatic shutdown of any generator se^ in the event of high jacket water temperature, low lube oil pressure, over-speed as determined by sensors mounted on the engine. Annunciation shall be included for the following "pre-alarm" and "acmal alarm" conditions:-

a. Low jacket water temperature - pre-alarm

b. High jacket water temperature — pre-alarm. -

c. Low lube oil pressure - pre-alarm.

d. Battery low voltage — pre-alarm.

e. Overcrank (engine failed to start) — actual alarm.

f. Over-speed - actual alarm (shutdown).

g- High jacket water temperature - actual alarm, (shutdown).

h. Low lube oil pressure ~ actual alarm (shutdown).

1. Reverse power - actual alarm (shutdown).

j- Failure to parallel - actual alarm.

k. Circuit breaker lockout — actual alarm.

1. Sums only indicator as follows:

Controls not in Automatic Flashing Red

Circuit Breaker Open Sums Green Circuit Breaker Closed Sums Red Engine Running Sums White Circuit Breaker Closed Failure Sums Red Control Voltage Failure Sums Red Auto Start Sums White

Spare lights shall be furnished for a total of twenty-four.

OEM PPS-26 Generators 7 WTC March 20, 1998

NYC-WTC_000166901

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000166901Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Electrical proposal, ADCO Electrical Corp., May 1998 · Box 7DCAS

NYC-WTC_000172686

Revised electrical work proposal from ADCO Electrical Corporation for the Mayor's Office of Emergency Management on the 26th floor at 7 World Trade Center in May 1998.

2 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.881

machine-extracted · confidence unavailable · Check page ↗
HVAC specification supplement, unknown date · Box 7DCAS

NYC-WTC_000173223

Supplement to HVAC specifications detailing discharge plenum construction standards for emergency generators at the Mayor's Office of Emergency Management.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.879

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →