PPS-Generators
Ambient Temperature In 110°
Generator Housing \yith
Machine Running.
Fuel Rating 19,250 BTU/Lb
Fuel Consumption Per Kilowatt------- 0.7 Lbs./Hr. (0.1 Of Certified Load (GPH)
Combustion Air Intake Per •5.0 CFM.
Kilowatt of Certified Load
Exhaust Gas Flow Per 15.0 CFM.
Kilowatt of Certified Load
Maximum Friction Head Back --------- 3/4 Inch Mercury.
Pressure Permissible in
Exhaust Pipe Extension
(Excluding Muffler)
Temperature of Exhaust Gasses 1200°F.
Static Pressure In ------ One (1) Inch Water
Air Stream Leaving
Load Bank
Air Flow Through 100 CFM
Radiator Per Kilowatt
Of Certified Load
I. Each engine and generator set shall be "factory package" mounted on a rigid base
consisting of a full length skid or rail of structural steel on each side and cross bracing
members at each end. Stable spring mountings incorporating a minimum static deflection
of 2" shall be provided between the dunnage steel and the base to which the engine and
generator are fastened. The spring mountings shall incorporate neoprene acoustical pads
and leveling adjustments.
J. Include the mounting of generator breakers and battery chargers and all connections
between same and the generating sets as set forth in manufacturer's wiring diagrams and
instructions. Include power supply connections to block heaters and battery chargers. If
the battery is not factory installed, include the field installation of battery, battery rack(s)
and interconnecting cables.
OEM PPS-16 Generators
7 WTC March 20, 1998