-2-

6. There is no 15" D. 1 pipe. It should be 16" D.l. It is advised that it be class 56 pipe with push-on joints on concrete cradle. 7. All sewers in the area are combined sewers and should be labeled as such.

8. Show the size of the house connection from manhole No.7 to the flow adopter chamb­ er. The 8" connection from the reservoir to manhole No.l should not be bent. It should be straight. In case this flow is through a force main, a pressure relief manhole will be required before being discharged into manhole ifl as discussed in the meeting on July 2, 1987.

9. Use standard N.Y.C. D.E.P. catch basins instead of inlets. Show type of catch basins. It is preferable not to use more than two catch basins in series as shown on drawing No. C-13.

10. Delete profile for catch basin connections and house connections. Invert elevations for the proposed catch basins shall be determined in the field and as such should not be shown on the plans. 11» The profile for the proposed sewers as shown on drawing No.S-32 must be drawn in accordance with D.E.P. standards. It must show type of manholes, type of seWer,^ distance between manholes, slope, .^ize, surface elevation, cover,''bidding etc. All .profiles must be drawn with a vertical scale such that the informdiion/data can be properly interpreted. The scale l"=10'is too small.~' 12. Drawing Nos.S-33, S-34, S~35, S-36, S-60, S-61 and S-62 can not be checked as no structural computations per comment No.ll of our letter dated April 15, 1987 have been submitted to this office.

13. Comply with comment Nos.f^,9,12 and 13 of our letter dated April 15, 1987 to you. All sewers having cover of less than 4.0' need to be encased or submit structural computations that the proposed sewers can take the load at the proposed cover of less than 4.0'. Submit easement and maintenance agreements.

NM NYC-WTC_000165350

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000165350Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →