14. The sections as shown on drawing No. S-33 and S-35 for the proposed 3'-6" X 3’-6" and 6"-0" X 4'-0" comb, sewers have a flat bottom. This is no good. They must have a V at the bottom per N.Y.C.D.E.P. standards. / w j 15. Show P.T., P.C., R,^,T for all the proposed chambers as shown on drawing Nos. ! f /.<< S-33,S-34, S-3S and S-36 as was requested in a meeting held in this office on July ’' 2, 1987. Tlxe details as shown do not meet the guidelines for the design of chambers as set forth by this department, a copy of which was given to you. The curves are too sharp. If the sizes of the proposed chambers change too much, revised structural computations, signed and sealed by a N.Y.S.P.E. will be required. 16. The proposed 3'-6" X 3'-6" and 6'-0" X 4'-0" cone, boxes are monolithic structures. Tlxerefore the reinforcement from the bottom and top slabs should be carried into the walls of the proposed box sewers. Show the details of the access manhole and chimney on all the chambers on drawing Nos. S-33,S-34,S-35 and S-36. It is prefer­ able to provide an opening on the flow redirection chamber near chamber No. 3 for maintenance purposes. 17. Show sections as marked in red on drawing Nos. S-33,S-34,S-35 and S-36 so as to show the details on the other opening. Show sections through the wiers and also show the details. 18. A sample for inverted siphon design was given to you. Your inverted siphon design is far different in many aspects that are not acceptable to this department.' (i) The 16" D.I.P, sanitary pipe can not be carried into the proposed twin 6'-0" X 4'-0" comb, sewer U/S of maintenance chamber A. The clean out can not be cleaned by this arrangement. The 16" D.I.P. sanitary sewer must start in the maintenance chamber A as given in the sample. The wier location also should correspond to the same. (ii) The wier as shown D/S end in maintenance chamber is also not acceptable. Its location must be per sample given to you. The clean out can not be cleaned because of the proposed 16" sanitary sewer being in the way. (iii) Show the details of the clean out as per sample. (iv) Show different sections and details as were provided to you in the sample. Submit roof plan for chambers'A and B. y i9. Sections C and F as shown on drawing No. S-34 should be rotated 90° to match the details on drawing No. S-33.

NYC-WTC_000165347

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000165347Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →