NYC 9/11 Public Portal Document
SECTION 02082
b) When the work area passes the Construction Manager visual reoccupancy
inspection, air sampling shall not begin until at least one (1) hour after the area is
dry from the wet cleaning. The testing laboratory shall perform air monitoring
using aggressive testing techniques. Reoccupancy will be approved by the
Construction Manager if the specified fiber count in the work area is achieved
according to the testing laboratory.
c) A minimum of five PCM and five TEM air samples will be collected inside the
work area to determine final air clearance reocupancy, provided that the amount
of ACM is greater than 160 square feet or 260 linear feet. All PCM and TEM
results must satisfy the clearance criteria for reoccupancy.
d) When volumes greater than or equal to 1,199 liters for a 25 mm filter and/or 2,799
liters for a 37 mm filter have been collected and all the TEM samples inside the
abatement area is less than 70 s/mm^ of filter, the abatement work shall be
considered complete without comparing the inside samples to the outside
samples.
e) When the work area passes the reoccupancy test, all controls and seals established
shall be removed.
B. Clearance Procedure for Areas Prepared Utilizing Tent Enclosure:
1. Clearance Procedure for Areas Prepared Utilizing Tent Enclosure:
a) Cleaning of the work areas and other contaminated areas shall be conducted in
accordance with procedure described below:
Step 1. Clean-up Visual Inspection
Step 2. Final Visual Inspection and fiber reoccupancy clearance count of <0.01
fiber/cc of air using NIOSH Method 7400 and less than 70 structures per
mm^ when using Transmission Electron Microscopy.
b) Area air samples will be collected prior, during and after abatement according to
established air clearance criteria per New York City Title 15.
c) To determine final air clearance reoccupancy, the following air samples shall be
collected for each tent (provided that the amount of ACM is less than or equal to
160 square feet or 260 linear feet):
Eive (5) PCM samples - inside work area
Three (3) TEM samples - inside work area
Three (3) PCM samples - outside work area
Three (3) TEM samples - outside work area
All PCM and TEM results must satisfy the clearance criteria for reoccupancy.
02082-45
CITY_21 MCI 00_014563818
NYC-WTC_000454618