as needed to maintain a fixed temperature of air entering the building . This control, typically set at 55’Fto 6O'F, provides ventilating during the cooling mode of operation. 1. HVAC Retrofit Solutions The present HVAC system configuration requires that the smoke purge system and the corridor HVAC systems function together to ensure the fire safety of the building. Therefore, the use of the existing central corridor air handlers to serve the classrooms to improve the outside air filtering is not considered to be a viable engineering solution. The design intent shown on the design drawings, and described in Section 3, was verified at the school on Tuesday, February 19, 2002. Ceiling tiles were removed in representative areas to verify that the HVAC systems are installed as shown on the original design drawings.

Increase Air Filtration of Existing Unit Ventilators The ability of the schools classroom's unit ventilator system to provide adequate “indoor air quality” and sufficient airborne particulate matter filtering is based on the United States Environmental Protection Agency (EPA) Particulate Matter (PM) promulgated health standards based on particulate matter with a diameter smaller than 2.5 microns’’ The present standard has been established by the EPA. The Bureau of Air Quality Surveillance is responsible for the operation of the ambient air quality monitoring network for the State of New York. The information obtained from the network is used to determine the attainment status of ozone (O3), sulfur dioxide (SO2), nitrogen oxides (NOx), carbon monoxide (CO), lead, and particulate matter. The EPA has promulgated health-based standards for the concentration of PM-2.5 in the atmosphere. The 24-hour average Standard has been set at 65 ug/m'’ (micrograms per cubic meter).. The more stringent EPA requirement of particulate matter of 40 ug/m3 (micrograms per cubic meter) that is applicable to children and adults with asthma or other respiratory health conditions was the intended filtration rate to be achieved with the retrofit filtration program. Daily environmental monitoring of the school’s indoor air quality indicates that these goals have been achieved’'*. However, a supplementary program has been developed to increase the filtration capability to meet a 95% particulate removal rate at 1 micron.

The proposed program offers significant advantages to the existing classroom unit ventilator HVAC system and does not interfere with the existing exhaust air or smoke purge systems of the building. The barometric relief damper will also insure proper room pressurization should outside air increase over the exhaust air system capabilities. The program consists of the following:

Typical Classroom (725 SF)

A micron is one millionth of a meter in diameter. See attached ATC air monitoring data and particulate sampling data

DOE00048139.DOC Appendix 1 - Page 22

CITY_21MC100_011284793

NYC-WTC_000453569

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000453569Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →