The existing HVAC system consisting of two floor mounted unit ventilators with an outside air requirement of 525 cfm will be retrofitted with a program consisting of the following: Conversion of one of the two existing floor mounted unit ventilators to a fan coil unit and the elimination of the introduction of outside air by this unit. Installation of a new vertical unit ventilator having the following characteristics. Combination Hydronic Heating coil and Chilled water coil Supply air requirement of 1250 to 1500 cfm depending on classroom size. Outside air heating capability of 50% of design cfm Filtering: 2” OdorGuard III pre-filter and 12” cartridge after filter (95% efficiency at 1 micron) Variable speed fan motor with sufficient design static for the two system filters and supply cfm directly related to room temperature requirements. Demand ventilation control based on room CO levels. Economizer control capability (100% outside air free cooling) Barometric relief damper to insure proper room pressurization. LonMark controls system for future Direct Digital Control (DDC) interface The proposed system configuration is illustrated in Figure 1.

Installation of the Vertical Unit Ventilator (VUV) will require the blocking of one classroom window as shown in Picture 1. Return air is introduced at the bottom of the VUV and outside air is introduced near the middle utilizing the bottom window sash to accommodate the outside air louver. The mixed air would be filtered using the 2” OdorGuard III activated charcoal pre-filter for odor and Volitale organic chemicals (VOC) control. A dual direct drive centrifugal fan would provide the required design airflow and static pressure to blow through the heating/cooling coil and the 12” deep cartridge after filter. Supply air would be discharged at the top of the unit in a more efficient throw pattern than possible with the floor-mounted unit.

Typical Large Classroom (LOOP SF) The existing HVAC system consist of three floor mounted unit ventilators with an outside air requirement of 725 cfm. The retrofit program consist of the following: Conversion of two of the three existing floor mounted unit ventilators to fan coil units and the elimination of the introduction of outside air by these units. Removal and replacement of one existing unit with one new unit to a new vertical unit ventilator having the following characteristics. Combination Hydronic Heating coil and Chilled water coil

DOE00048139.DOC Appendix 1 - Page 23

CITY_21MC100_011284794

NYC-WTC_000453570

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000453570Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →