units as normally required by current School Construction Authority (SCA) guidelines. A percentage of the outside air introduced into the building from HVAC-1 and HVAC-2 and the unit ventilators are also used as transfer air for the local toilet exhaust systems.

The corridor HVAC-1 and HVAC-2 and classroom HVAC systems are interfaced to a smoke purge system per SCA guidelines. The smoke purge system consists of smoke purge fans F3 (87,625 cfm), F4 (87,625 cfm) and F5 (44,300 cffn). Smoke exhaust fans F3 and F4 are connected to a common smoke/relief riser identified as (S-R1) on the design drawings. Smoke exhaust fan F5 is connected to a common smoke/relief riser identified as (S-R2) on the design drawings.

Each riser has a fire/smoke damper in the corridor ceiling plenum. In addition, each classroom is provided with a transfer grille connected to the corridor ceiling plenum to provide a means of purging each classroom on a floor by floor basis. The transfer grilles are provided with fire dampers.

In the fire smoke purge mode, all supply fans are automatically shut down thus eliminating the introduction of mechanically induced outside air. The fire/smoke dampers of the smoke purge systems are coordinated by the fire department to exhaust air on an individual floor basis.

A1.2 Application of Unit Ventilators

Unit ventilators are a type of HVAC terminal equipment that uses a centrifugal blower, a finned-coil heating/cooling exchanger, and an air filter. The specific equipment package installed in Stuyvesant High School is a two-pipe single coil system that uses hot water from a central boiler for heating and chilled water from a central chiller for air conditioning.

Unit ventilators are very popular for rooms requiring large amounts ventilation air, such as classrooms, since system ductwork is not required, and outside air is provided directly from the outside air grille. Other advantages and system benefits inherit with this type of terminal system include:

• Lower installed costs compared to central air systems or more complex four-pipe multiple coil systems. • Conditioning and temperature control on a room by room basis and the ability to introduce 100% outside air for economy cooling cost effectively. • System controls are provided on a unitary basis providing flexibility and diversification. Each room occupant can control fan speed on a unit by unit basis and unit capacity is provided in direct response to room temperature requirements. Disadvantages of this type of terminal system include limited system filtration due to filter track width and static pressure capability of the unit’s fan system. Other disadvantages with this type of terminal system include:

A:\6_RstroflttingHV AC_R.CascoM.doc

Page A1-2

CITY_21MC1OO_O1O2742O5

NYC-WTC_000278818

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000278818Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →