6.05 Unit Ventilators A schematic of a unit ventilator is provided in Figure 2. These terminal systems are popular for high density occupant spaces such as classrooms since they are able to provide large amounts of outside air economically without extensive central system ductwork. Their unitary design, on a classroom by classroom basis, also permits the design engineer to provide cooling and heating on a zone by zone basis and also provides the proper use of economy cooling to offset different space heating heating/cooling loads. The space load diversity due to exposure orientation, internal heat gains and outside air requirements based on the number of occupants and specialized local exhaust requirements such as fume hoods, computers, etc. can be properly provided by the unit ventilators. These units are also typically provided with multi-speed fan controls to provide system capacity in addition to modulated valve control.
The basic system design consist of two and four pipe systems with typically low temperature hot water (180 to 2OO’F) and chilled water (45’F) as the preferred heating/cooling media. Low pressure steam (5 lbs) is also a common heating media and Direct Expansion (DX) air-conditioning is an alternate cooling media where central chilled water plants are not economically feasible.
The advantage of the four pipe system vs. the two pipe system is that heating and cooling can be provided at the same time to different zones of the building due to their unique heating and cooling loads during intermediate seasons.
The two-pipe system, however, is more prevalent since it is more cost effective and the simultaneous use of heating and cooling has been less prevalent as an energy reduction measure. Application of the two-pipe system requires the building operator to be more conscience of the building heating and cooling loads and its response to variations in outside air temperature variations.
Major system disadvantages include: o Limited filtration due to fractional motor horsepower and filter tracks width o Potential freeze protection due to piping and coil exposure to ambient outside air conditions.® o Increased number of units to be maintained compared to central systems
® This limitation is normally countered by the use of ethylene glycol in the heating/cooling water.
A:V8_RotronMn9HVAC_R.CttftcoM>.doe
Page 16
CITY_21MC1OO_OO9O93O95
NYC-WTC_000322261
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
34 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000453548
Board of Education disaster response summary for schools near WTC site.
22 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000276036
Document discussing lessons learned in children's environmental health related to Ground Zero sites.
28 shared non-person entities · 1 shared topics · similarity 0.959
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000319809
Document describing MS/PS 85M occupancy and recovery operations related to WTC.
21 shared non-person entities · similarity 0.959
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000125845
Draft fact sheet from DOH and DEP addressing tenant concerns regarding asbestos fibers at 105 Duane Street.
17 shared non-person entities · 1 shared topics · similarity 0.952
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000317925
Draft chain-of-custody outlining ambient and residential dust sampling near WTC with exposure rationale.
11 shared non-person entities · similarity 0.952
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236896
Draft protocol document outlining daily ambient air and dust sampling procedures for PS/IS 89 following the World Trade Center tragedy.
10 shared non-person entities · similarity 0.951
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000104673
Report from Consulting & Testing Services, Inc. regarding air quality monitoring at NYU Downtown Hospital in September 2001.
7 shared non-person entities · similarity 0.951
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000145027
Notice from NYC Law Department instructing staff to preserve World Trade Center documents for potential legal actions.
14 shared non-person entities · 1 shared topics · similarity 0.950
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250253
ATC cost estimate letter for environmental services at six schools affected by 9/11.
10 shared non-person entities · similarity 0.948
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000106330
Letter reporting asbestos testing results for air and dust at Borough of Manhattan Community College in February 2002.
15 shared non-person entities · similarity 0.948
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000106411
Union memorandum regarding environmental monitoring and cleanup protocols following the closure of Stuyvesant High School after the September 11 attacks.
11 shared non-person entities · 1 shared topics · similarity 0.948
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000453548
Board of Education disaster response summary for schools near WTC site.
Similarity score 0.963 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000453548
Board of Education disaster response summary for schools near WTC site.
Similarity score 0.958 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000453548
Board of Education disaster response summary for schools near WTC site.
Similarity score 0.950 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000453548
Board of Education disaster response summary for schools near WTC site.
Similarity score 0.950 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similarity score 0.948 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similar indexed content
NYC-WTC_000453548
Board of Education disaster response summary for schools near WTC site.
Similar indexed content
NYC-WTC_000276036
Document discussing lessons learned in children's environmental health related to Ground Zero sites.
Similar indexed content
NYC-WTC_000319809
Document describing MS/PS 85M occupancy and recovery operations related to WTC.
Similar indexed content
NYC-WTC_000125845
Draft fact sheet from DOH and DEP addressing tenant concerns regarding asbestos fibers at 105 Duane Street.
Similar indexed content