Application of Unit Ventilators Unit ventilators are a type of HVAC terminal equipment that uses a centrifugal blower, a finned-coil heating/cooling exchanger, and an air filter. The specific equipment package installed in Stuyvesant High School is a two-pipe single coil system that uses hot water from a central boiler for heating and chilled water from a central chiller for air conditioning. Unit ventilators are very popular for rooms requiring large amounts ventilation air, such as classrooms, since system ductwork is not required, and outside air is provided directly from the outside air grille. Other advantages and system benefits inherit with this type of terminal system include: Lower installed costs compared to central air systems or more complex four-pipe multiple coil systems. Conditioning and temperature control on a room by room basis and the ability to introduce 100% outside air for economy cooling cost effectively. System controls are provided on a unitary basis providing flexibility and diversification. Each room occupant can control fan speed on a unit by unit basis and unit capacity is provided in direct response to room temperature requirements. Disadvantages of this type of terminal system include limited system filtration due to filter track width and static pressure capability of the unit’s fan system. Other disadvantages with this type of terminal system include: System changeover is required from heating to cooling during the intermediate seasons. System may not be able to respond to drastic weather variations due to the temperature control required to protect boilers from low water temperature conditions and chillers from high temperature conditions. Due to infiltration, malfunctioning outside air dampers, and other maintenance and operations problems, freeze-up of the unit's coils may be a problem during the unoccupied temperature setback periods.
Temperature Control Control sequences of operations are very flexible and include the following three basic control cycles defined as: Cycle 1: 100 percent outdoor air is admitted for economy cooling during the occupied mode of operation. During warm-up the outside air damper is closed. Cycle II: A minimum amount of outside air (20 to 50%) is admitted during the occupied mode of operation for heating and ventilating. The percentage of outdoor air is gradually increased, in response to a rise in space temperature. As additional space cooling is required, the heating valve is modulated close and the outside air damper is modulated to 100% open to provide economy cooling. During warm-up the outside air damper is closed. Cycle III Except during the warm-up stage, a variable amount of outdoor air is admitted
DOE00048139.DOC Appendix 1 - Page 21
CITY_21MC100_011284792
NYC-WTC_000453568
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000250253
ATC cost estimate letter for environmental services at six schools affected by 9/11.
16 shared non-person entities · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250241
Laboratory report page with OCR-garbled content; appears to be environmental test results related to PS 89M.
16 shared non-person entities · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
32 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
22 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000276036
Document discussing lessons learned in children's environmental health related to Ground Zero sites.
27 shared non-person entities · 1 shared topics · similarity 0.957
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000455806
Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.
9 shared non-person entities · similarity 0.947
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236896
Draft protocol document outlining daily ambient air and dust sampling procedures for PS/IS 89 following the World Trade Center tragedy.
16 shared non-person entities · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000319809
Document describing MS/PS 85M occupancy and recovery operations related to WTC.
16 shared non-person entities · similarity 0.943
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385830
protocol for ambient air and dust sampling inside PS 89 Manhattan following WTC cleanup.
16 shared non-person entities · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274908
Draft ambient air/dust sampling protocol for asbestos at Stuyvesant High School.
15 shared non-person entities · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000145027
Notice from NYC Law Department instructing staff to preserve World Trade Center documents for potential legal actions.
16 shared non-person entities · 1 shared topics · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385871
Ambient air and dust sampling protocol for High School for Leadership & [name] (M 894).
16 shared non-person entities · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similar indexed content
NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
Similar indexed content
NYC-WTC_000276036
Document discussing lessons learned in children's environmental health related to Ground Zero sites.
Similar indexed content
NYC-WTC_000455806
Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.
Similar indexed content
NYC-WTC_000236896
Draft protocol document outlining daily ambient air and dust sampling procedures for PS/IS 89 following the World Trade Center tragedy.
Similar indexed content