6.05 Unit Ventilators A schematic of a unit ventilator is provided in Figure 2. These terminal systems are popular for high density occupant spaces such as classrooms since they are able to provide large amounts of outside air economically without extensive central system ductwork. Their unitary design, on a classroom by classroom basis, also permits the design engineer to provide cooling and heating on a zone by zone basis and also provides the proper use of economy cooling to offset different space heating heating/cooling loads. The space load diversity due to exposure orientation, internal heat gains and outside air requirements based on the number of occupants and specialized local exhaust requirements such as fume hoods, computers, etc. can be properly provided by the unit ventilators. These units are also typically provided with multi-speed fan controls to provide system capacity in addition to modulated valve control.

The basic system design consist of two and four pipe systems with typically low temperature hot water (180 to 2OO’F) and chilled water (45’F) as the preferred heating/cooling media. Low pressure steam (5 lbs) is also a common heating media and Direct Expansion (DX) air-conditioning is an alternate cooling media where central chilled water plants are not economically feasible.

The advantage of the four pipe system vs. the two pipe system is that heating and cooling can be provided at the same time to different zones of the building due to their unique heating and cooling loads during intermediate seasons.

The two-pipe system, however, is more prevalent since it is more cost effective and the simultaneous use of heating and cooling has been less prevalent as an energy reduction measure. Application of the two-pipe system requires the building operator to be more conscience of the building heating and cooling loads and its response to variations in outside air temperature variations.

Major system disadvantages include:

• Limited filtration due to fractional motor horsepower and filter tracks width • Potential freeze protection due to piping and coil exposure to ambient outside air conditions.®

• Increased number of units to be maintained compared to central systems

’ This limitation is normally countered by the use of ethylene glycol in the heating/cooling water.

A:\6_R0trafmingHVAC_R.Cftscorw.doe

Page 16

CITY_21MC100_010274194

NYC-WTC_000278807

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000278807Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →