6.06 Filtration Program The filtration program required for the BOE unit ventilators included the following:

School No. of Unit Ventilators

Stuyvesant High School 300 IS/PS 89 100 PS234 4 PSI 50 Tribeca Learning Center PreK-5 12 Preliminary investigation indicated that upgrading the unit ventilators to meet the desired indoor air quality criteria, without extensive system modifications, would be difficult due to the limited system static capability and filter track provided by the existing units.

The existing units were provided with fractional horsepower motors (1/8 to % HP) that provided approximately 700 to 1000 cfm of supply air based on their system design.

The filtration provided was limited to a 1” wide filter rack using disposable fiberglass filer media with a MERV rating of 1. The existing filters were functioning as protection for the systems coils with no consideration of indoor air quality.

The main objective of the unit ventilator filter upgrade program was to investigate several design options that would increase the efficiency of the unit ventilator systems to meet the design criteria.

To accomplish this the first design task was to modify the existing filter track from al” wide track to a 2” track to accommodate a wider and thus more efficient filter. The second design task was to select a replacement filter for the unit ventilators.

7.0 Scope of Work for Unit Ventilator Testing The program for testing the efficacy of various types of filters to be used in the unit ventilators for PS89 and Stuyvesant High School is provided in this report section.

7.01 Methodology

Four classrooms in PS 89 were converted from 1” wide tracks to 2” tracks as a test facility to establish the optimum replacement filter and to enhance the filtration of the outdoor air for classroom ventilation. The filter media in the existing unit ventilator is 9” wide x 36” long. The program consists of testing four different types of Unit ventilator filters in four classrooms at PS 89.

Increasing the existing filter racks to 2” racks enabled the Bd. of Ed. to consider various types of filters and to use a combination of carbon activation for odor control and media

A:>6_R«tromtingHVAC.R.CascotM.doc Page 17

CITY_21MC100_0 10274195

NYC-WTC_000278808

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000278808Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →