Scope of Work for Unit Ventilator Testing

The program for testing the efficacy of various types of filters to be used in the unit ventilators for PS89 and Stuyvesant High School is provided in this report section.

Methodology Four classroom in PS89 were converted from 1” wide tracks to 2” tracks as a test facility to establish the optimum replacement filter and to enhance the filtration of the outdoor air for classroom ventilation. The filter media in the existing unit ventilator is 9” wide x 36” long. The program consists of testing four different types of Unit ventilator filters in four classrooms at PS 89.

Increasing the existing filter racks to 2” racks enabled the Bd. of Ed. to consider various types of filters and to use a combination of carbon activation for odor control and media filter for particulate filtering.

ATC, the BOE environmental consultants, monitored four (4) classrooms in PS89 for particulate on a continuous basis for a 2 week period. Particulate values were taken on a 15-minute interval, data logged and plotted for comparison*’.

The testing program consisted of the following:

PS89 Sampling Program - Particulate Four classrooms on the L‘ floor, hotel side of the school were sampled

Filters tested consisted of the following: Classroom 1: Original 1” filter media to serve as baseline. Classroom 2: 2” Odor Guard III as provided by Air Engineering: 2”- 9" x 36". Classroom3: Modified Odor Guard III filter 9"x36"modified as follows: Removed existing media and inserted 4 ply-pleated media as provided by Air Engineering. Classroom 4: One Classroom with McQuay provided Electrostatic Filter.

Sampling was conducted between ** and ***. The results of the program is tabulated below:

***TO BE DEVELOPED AND INCORTPORATED

® See Appendix

DOE00048139.DOC Appendix 1 - Page 18

CITY_21MC100_011284789

NYC-WTC_000453565

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000453565Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →