filter for particulate filtering.

ATC, the BOE environmental consultants, monitored four (4) classrooms in PS89 for particulate matter (PM 2.5) on a continuous basis for a 1 week period. Particulate values were taken on a 15-minute interval, data logged and plotted for comparison^®.

The testing program consisted of the following:

7.1.1 PS89 Sampling Program - Particulate Four classrooms on the 1®' Floor, hotel side of the school were sampled using Dust Trak® Model 8020 Aerosol Monitors manufactured by TSI, Inc. The Dust Trak is a data logging particulate measuring device with a size-selective inlet port.

Filters tested consisted of the following:

• Classroom 304: Original 1” filter media to serve as baseline • Classroom 404: 2” Odor Guard III as provided by Air Engineering: 2”-9'' x 36" « Classroom 306: Modified Odor Guard III filter 9''x36"modified as follows: • Removed existing media and inserted 4 ply-pleated media as provided by Air Engineering.

• Classroom 406: One Classroom with McQuay provided Electrostatic Filter.

The results of the program is tabulated below:

MINIMUM AVERAGE MAXIMUM TOTAL TIME LOCATION/FILTER TYPE {pg/m^} {pg/m’} {pg/m’} SAMPLED HOURS

Room 304/Original Uni-vents off 27 29 30 1 Hr. 3 Min. Baseline Blue Uni-vents on 5 18 34 166 Hrs. 2 Min. Room 306/Odorguard III + Uni-vents off 23 24 25 1 Hr. 3 Min. 4 ply filter Uni-vents on 8 20 37 166 Hrs. 17 Min. Room Uni-vents off 16 18 19 1 Hr.12 Min. 404/Odorguard III Uni-vents on 3 15 34 111 Hrs. 30 Min. Room 406/McCuay Uni-vents off 14 15 16 1 Hr. 11 Min. Eleclostatic Uni-vents on 8 18 32 166 Hrs. 30 Min.

” See Appendix

A;»_RetronttingHVAC_R.Cascone.doc

Page 18

CITY_21MC1OO_OO9O93O97

NYC-WTC_000322263

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000322263Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →