Retrofitting HVAC Systems, WTC, QA dokument

Machine-extracted title · confidence 38%

Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.

NYC-WTC_000322244–000322270
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

During the period of sampling, outside air particulate matter was recorded in the range of 20 to 35 pg/m^. The maximum indoor levels were consistent with the recorded outdoor levels.

Observation of the data indicates that the OdorGuard III carbon activated filter provided the overall best performance with a performance of 3 {pg/m^} for the minimum level recorded over the testing period and 15 pg/m^ for the average particulate level over the testing period.

Increasing the particulate media of the OdorGuard II by adding a 4-ply pleated filter resulted in significant filter bypass thus resulting in the higher test readings.

Although the McQuay electrostatic filter had similar test results than the OdorGuard III filter, the OdorGuard III filter was chosen based on ease of installation, and maintenance cost considerations.

8.0 Filter Upgrade Program

8.01 Background Information As previously described , the BOE classrooms provided with unit ventilators also have specialized laboratories and other rooms requiring special conditioning requirements.

As part of the air filtration rehabilitation program the filtration of these units were increased by modifying the existing filter rack from one to two inches in width. This modification permitted the installation of the Odor Guard III filters^that were used extensively as central air handler pre-filters with satisfactory results. The Odor Guard III filter is a three-ply carbon activated filter designed to remove particulate and VOC's; thus is an effective odor control filter.

The need for carbon activated filters in lieu of a particulate filtering only was due to the schools proximity to the location of the diesel crane being used to load debris from the World Trade Center construction site to barges. The diesel fumes emanating from the cranes have been a constant source of odor complaints within the schools in close proximity to the barge site

In addition to the identified odor problems, concern for increasing the filtration of the classroom unit ventilators was considered due to: Proximity to World Trade Center (WTC) and associated particulate emissions from the site. © Proximity to vehicle transportation route for debris removal from the WTC site. e Proximity to diesel exhaust emissions from the barge debris removal operations.

” See Manufacturers Literature Appendix 1

A:\9.Ro4rofinin8HVAC_R.Ca$cone.do6 Page 19

CITY_21MC1OO_OO9O93O98

NYC-WTC_000322264

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000322264Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →