These filters also produced by the Tri-Dim Corporation and are identified as Tri-Dem Syn-Pac Filter. Filter size is 24”x24”x 30 inches deep. At 1 micron this filter has a MERV efficiency of 97% and an initial resistance of .1.0 w.g.; ASHRAE test data was at 500 fpm

8.03 Unit Ventilators The existing unit ventilators were provided with 1” filter racks that limited the amount of filtration feasible for reducing particulate counts in the classrooms served by unit ventilators in lieu of central air handlers.

The concept of using the Odor Guard carbon activated filter was developed as a feasible design alternative. This required modifications of the existing 1” filter racks to a 2” wide rack to accommodate the 2” wide Odor Guard III filters.

Verification of the effectiveness of the filter program was verified by particulate measurements as summarized below;

Measurement of Airborne Particles - Indoor Air Quality

Date: Wednesday, January 23, 2002

Indoor air quality measurements were taken using a ParticleScan laser particle counter to monitor and verify the performance of the new filtration installed in PS234 and Stuyvesant High School.

Baseline Measurements were taken amid December and indicated that the outside particle count at .3 micron/ cubic meter was approximately 3,000,000 to 3,500,000 in the outside air and approximately 1,500,000 to 2,000,000 inside the schools before the filter retrofit program.

After the filter retrofit program as indicate below the following particle count were measured.

PS234

Outside Air - 1.400.000 Reduction of 60% (Cleanup of WTC Site)

PARTICLE FILTER ROOMS COUNT TYPE LOCATION RESULTS

323 600.000 2" Odor Guard - 2” 4 ply Pleat Classroom 66% Reduction of Particulate 301 607,000 2" Odor Guard - 2” 4 ply Pleat Classroom 66% Reduction of Particulate 201 573, 2” Odor Guard - 2” 4 ply Pleat Library 67% Reduction of Particulate Auditorium 645,000 2” Odor Guard - 2” 4 ply Pleat Auditorium 63% Reduction of Particulate

A;^6_R«troftttlngHVAC_R.Cascon«.doc

Page 21

CITY_2IMC10 0_010 2 7 419 9

NYC-WTC_000278812

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000278812Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →