NYC 9/11 Public Portal Document

Upgrade Program for Unit Ventilator Design

Backgronnd Information

As previously described , the BOE classrooms provided with unit ventilators also have specialized laboratories and other rooms requiring special conditioning requirements. As part of the air filtration rehabilitation program the filtration of these units were increased by modifying the existing filter rack from one to two inches in width. This modification permitted the installation of the Odor Guard III filters^® that were used extensively as central air handler pre-filters with satisfactory results. The Odor Guard III filter is a three-ply carbon activated filter designed to remove particulate and VOC's; thus is an effective odor control filter. The need for carbon activated filters in lieu of a particulate filtering only was due to the schools proximity to the location of the diesel crane being used to load debris from the World Trade Center construction site to barges. The diesel fumes emanating from the cranes have been a constant source of odor complaints within the schools in close proximity to the barge site

In addition to the identified odor problems, concern for increasing the filtration of the classroom unit ventilators was considered due to: Proximity to World Trade Center (WTC) and associated particulate emissions from the site. Proximity to vehicle transportation route for debris removal from the WTC site. Proximity to diesel exhaust emissions from the barge debris removal operations.

The following report section investigates methods of increasing the filtration of the classrooms unit ventilation units to 95% filtration efficiency” as a long term solution to the present HVAC situation. Stuyvesant High School was used as a case study example.

Description of Existing HVAC Systems The Stuyvesant High School heating, ventilating, and air conditioning (HVAC) systems consist of central air handlers as scheduled in Table 1 and Unit Ventilators as summarized in Table 2. The central air handlers serve HVAC for the school corridors, gymnasium, auditorium, and other specialized use areas of the building as shown in Table 1. Unit ventilators are provided for HVAC the school’s classrooms and offices in both the horizontal ceiling mounted types (Types E, F, G, H) and floor mounted cabinet types (A, B, C, D, I, J, K, IThe horizontal ceiling mounted unit ventilators are generally used to

See Manufacturers Literature Appendix 1 " Efficiency of filters evaluated per ASHRAE 52.2 (1 Micron particle size) ’2 See Table 3

DOE00048139.DOC Appendix 1 - Page 19

CITY_21MC100_011284790

NYC-WTC_000453566

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000453566Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →