Upgrade Program for Unit Ventilator Design
Backgronnd Information
As previously described , the BOE classrooms provided with unit ventilators also have specialized laboratories and other rooms requiring special conditioning requirements. As part of the air filtration rehabilitation program the filtration of these units were increased by modifying the existing filter rack from one to two inches in width. This modification permitted the installation of the Odor Guard III filters^® that were used extensively as central air handler pre-filters with satisfactory results. The Odor Guard III filter is a three-ply carbon activated filter designed to remove particulate and VOC's; thus is an effective odor control filter. The need for carbon activated filters in lieu of a particulate filtering only was due to the schools proximity to the location of the diesel crane being used to load debris from the World Trade Center construction site to barges. The diesel fumes emanating from the cranes have been a constant source of odor complaints within the schools in close proximity to the barge site
In addition to the identified odor problems, concern for increasing the filtration of the classroom unit ventilators was considered due to: Proximity to World Trade Center (WTC) and associated particulate emissions from the site. Proximity to vehicle transportation route for debris removal from the WTC site. Proximity to diesel exhaust emissions from the barge debris removal operations.
The following report section investigates methods of increasing the filtration of the classrooms unit ventilation units to 95% filtration efficiency” as a long term solution to the present HVAC situation. Stuyvesant High School was used as a case study example.
Description of Existing HVAC Systems The Stuyvesant High School heating, ventilating, and air conditioning (HVAC) systems consist of central air handlers as scheduled in Table 1 and Unit Ventilators as summarized in Table 2. The central air handlers serve HVAC for the school corridors, gymnasium, auditorium, and other specialized use areas of the building as shown in Table 1. Unit ventilators are provided for HVAC the school’s classrooms and offices in both the horizontal ceiling mounted types (Types E, F, G, H) and floor mounted cabinet types (A, B, C, D, I, J, K, IThe horizontal ceiling mounted unit ventilators are generally used to
See Manufacturers Literature Appendix 1 " Efficiency of filters evaluated per ASHRAE 52.2 (1 Micron particle size) ’2 See Table 3
DOE00048139.DOC Appendix 1 - Page 19
CITY_21MC100_011284790
NYC-WTC_000453566
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000250253
ATC cost estimate letter for environmental services at six schools affected by 9/11.
16 shared non-person entities · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000250241
Laboratory report page with OCR-garbled content; appears to be environmental test results related to PS 89M.
16 shared non-person entities · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
32 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
22 shared non-person entities · 1 shared topics · similarity 0.987
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000276036
Document discussing lessons learned in children's environmental health related to Ground Zero sites.
27 shared non-person entities · 1 shared topics · similarity 0.957
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000455806
Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.
9 shared non-person entities · similarity 0.947
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000236896
Draft protocol document outlining daily ambient air and dust sampling procedures for PS/IS 89 following the World Trade Center tragedy.
16 shared non-person entities · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000319809
Document describing MS/PS 85M occupancy and recovery operations related to WTC.
16 shared non-person entities · similarity 0.943
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385830
protocol for ambient air and dust sampling inside PS 89 Manhattan following WTC cleanup.
16 shared non-person entities · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274908
Draft ambient air/dust sampling protocol for asbestos at Stuyvesant High School.
15 shared non-person entities · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000145027
Notice from NYC Law Department instructing staff to preserve World Trade Center documents for potential legal actions.
16 shared non-person entities · 1 shared topics · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385871
Ambient air and dust sampling protocol for High School for Leadership & [name] (M 894).
16 shared non-person entities · similarity 0.941
machine-extracted · confidence unavailable · Check page ↗Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similarity score 0.977 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
Similarity score 0.975 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similarity score 0.963 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
Similarity score 0.962 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similarity score 0.955 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
Similarity score 0.953 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000278790
New York Council report on retrofitting HVAC systems at Ground Zero for IAQ.
Similar indexed content
NYC-WTC_000322244
Consulting report cover page for HVAC retrofitting and air quality at Ground Zero.
Similar indexed content
NYC-WTC_000276036
Document discussing lessons learned in children's environmental health related to Ground Zero sites.
Similar indexed content
NYC-WTC_000455806
Safety and health survey of a DOE office space and HVAC system following employee complaints at 52 Chambers Street.
Similar indexed content
NYC-WTC_000236896
Draft protocol document outlining daily ambient air and dust sampling procedures for PS/IS 89 following the World Trade Center tragedy.
Similar indexed content