8.02 Selection of Filtration Systems ASHRAE Standard 52.2 prescribes a method of testing air-cleaning devices for removal efficiency by particle size and the filter resistance to airflow. The test is conducted at a specified airflow and a corresponding selected velocity usually 500 fpm.

A composite performance curve is developed based on particle size removal efficiency performance curves and an initial performance curve over a range of particle sizes. Points on the composite curves are averaged and these averages are used to determine the Minimum Efficiency Reporting Value (MERV) of the air filter under testing. The Minimum Efficiency Removal Value (MERV Rating) is then used for comparison of different filter ability to provide particulate filtering, see Table 6-1.

Bums and Roe reviewed the HVAC central air handlers at the various schools and developed and filter modifications based on available filter rack size and by selecting filters of MERV rating that would provide the required filtration with the physical limitations of the central air handlers.

Based on a field survey of existing conditions, the baseline air balancing work the majority of the air handlers systems were provided with 2” filter racks in the mixed air stream. A few of the central systems had sufficient space for the installation of bag filters. Also, due to the presence of VOC’s due to the debris removal operations and VOC’s emanating from the World Trade Center site the use of a granular activated carbon filter for removal of gaseous pollutants and odors was of paramount consideration.

The selected pre-filter was the Odor Guard III manufactured by D-Mark Air Filtration Corporation.

The filter is 2” wide and has a carbon content of 300 grams per Square foot. At 500 feet per minute face velocity the filter has an initial resistance of .75 “ w.g. The filter is a three stage filtration product with a Primary %” polyester media for removal of particulate, a secondary carbon media, and a tertiary polyurethane foam media for arresting carbon particles.

New filter racks were constructed to accommodate primary filtering of outside air with the Odor Guard III carbon activated filter.

The central air handlers were provided with two sets of filtering. The existing 2” filter racks were provided with a 4 ply internal ring panel and link filter (Tri-Dek XL) manufactured by the Tri-Dim Corporation to provide after filtering. At 1 micron this filter has a MERV efficiency of 40% and an initial resistance of .26” w.g.; ASHRAE test data was at 300 fpm. A major advantage of this filter is that it is manufactured to the exact size requirement and configuration of the air handler facilitating installation and eliminating flow bypass around the filter rack that is common with 2x2 box type filters. The filter is approximately 1.5” deep.

Several of the schools air handlers had sufficient room to install larger bag filters. ATtfi_RotraflttingHVAC_R.Cascerw.doc

Page 20

CITY_21MC100_009093099

NYC-WTC_000322265

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000322265Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →