.i 5 i filter for particulate filtering. J ATC, the BOE environmental consultants^ monitored four (4) classrooms in PS89 for particulate matter (PM 2.5) on a continuous^basis for a 1 week period. Particulate values were taken on a 15-minute interval, data lodged and plotted for comparison^®.

The testing program consisted of the follovfting: I 7.1.1 PS89 Sampling Program - Particulalp Four classrooms on the 1®* Floor, hotel side of the school were sampled using Dust Trak® Model 8020 Aerosol Monitors manufactured by TSI, Inc. The Dust Trak is a data logging particulate measuring device with a size-selective inlet port. f. Filters tested consisted of the following:

• Classroom 304: Original 1” filter m^dia to serve as baseline

• Classroom 404: 2” Odor Guard III as provided by Air Engineering: 2”-9'’ x 36" • Classroom 306: Modified Odor Gu^rd III filter 9"x36''modified as follows:

• Removed existing media and inserted 4 ply-pleated media as provided by Air Engineering.

• Classroom 406: One Classroom with McQuay provided Electrostatic Filter. 1

The results of the program is tabulated be|ow:

MINIMUM AVERAGE MAXIMUM TOTAL TIME LOCATION/FILTER TYPE {pg/m’) SAMPLED HOURS

Room 304/Original Baseline Blue Uni-vents off F 29 30 1 Hr. 3 Min.

Uni-vents on '5 18 34 166 Hrs. 2 Min. Room I

306/Odorguard III + Uni-vents off 23 24 25 1 Hr. 3 Min. 4 ply filter 37 166 Hrs. 17 Min. Room Uni-vents on Uni-vents off A 16 20 18 19 1 Hr.12 Min. 404/Odorguard Ui Uni-vents on 3 15 34 111 Hrs. 30 Min. Room 406/McCuay Uni-vents off 15 16 1 Hr. 11 Min. Eleclostatic Uni-vents on '8 18 32 .166 Hrs. 30 Min.

See Appendix (

A:\6_n«trefinfn9HVAC_R.CescoM.doc

Pjage 18

CIT Y_21 MCI 001'6102 7 4196

NYC-WTC_000278809

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000278809Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →