NYC 9/11 Public Portal Document

In establishing the filtration requirements of the schools, and the Minimum Efficiency Rating Value (MERV) of the selected HVAC filters, Bums and Roe has used the more stringent EPA requirement of particulate matter of 40 ug/m3 (micrograms per cubic meter). This EPA requirement is applicable to children and adults with asthma or other respiratory health conditions.

ASHRAE Standard 62-2001 also specifies the allowable concentration of pollutants in ventilation air and requires treatment (filtering) to maintain the required “indoor air quality” should outside air exceed the allowable concentrations.

The EPA has established PM2.5 as the basis of establishing Fine Particulate Matter. Fine particulate matter is particles known to accumulate into human lung tissue.

- The monitoring program measured the following outdoor air contaminants and constituents that standards have been established set by the EPA for National Ambient Air Quality Standards. © Status of ozone (O3) © Sulfur Dioxide (SO2) © Nitrogen Oxides (NOx) © Carbon Monoxide (CO) © Lead © Particulate Matter - 2.5PM o Particle identification using microscopic techniques and scanning by electron microscope. Bums and Roe had substantial in situ airborne testing data that was available from the EPA monitoring network and published by the New York State Division of Air Resources and Bureau of Air Quality Surveillance. Within Region 2 (lower Manhattan), five monitoring stations^ provided 24 hour data on a continues basis. The Borough of Manhattan Community College is in close proximity to Stuyvesant High School, PS/IS89, and PS234 and was used as a benchmark to established the outdoor air quality that required filtering to meet the EPA 2.5 PM standard.

In addition to the continuous outdoor air monitoring program, conducted by the EPA, ATC an environmental consulting firm was under contract by the BOE to provide indoor air quality monitoring at Stuyvesant High School®. This was the first school to be re­ occupied after the WTC collapse on September 11th. An extensive daily indoor air quality program was established and reviewed by the BOE Department of Health and Safety on a 24-hour basis. The testing program consisted of: ® Monitoring classrooms for Carbon Monoxide (CO) and Carbon Dioxide (CO2)

5 Borough of Manhattan Community College, Park Row, Albany Street, Wall Street, Coast Guard Battery Park - See Exhibit 1 ® As additional schools were turned back to the BOE, ATC provided indoor monitoring at each additional school.

A:\6_RotrofmingHVAC_R.Cascono.doc Page 5 CITY_21MC100_009093084

NYC-WTC_000322250

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000322250Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →