Vertical Unit Ventilators Sequence of Operations Unoccupied Condition

During the “unoccupied heat” mode (night setback) space temperature shall be maintained by a master/slave interface to the existing horizontal fan coil units. On a call from the space temperature sensor (55’F adjustable setpoint) the heating modulation valves of the fan coils units shall be indexed open in relation to the demand for space heating. The Vertical Unit Ventilator will not operate in the unoccupied mode and its respective outdoor air damper shall be fully closed and the supply fan off. In the event the unoccupied space temperature falls below 5O’F (adjustable setpoint), the master control system shall cycle the slave horizontal coil units fans on until the unoccupied space temperature setpoint is satisfied (55’F adjustable).

Occupied Condition - Heating

The Vertical Unit Ventilator and associated slave fan coil units shall be indexed to the “occupied mode” by a room motion sensor. A passive infrared motion sensor incorporated into the space temperature controller shall detect motion. After an adjustable Time-Out-Delay (TOD) period, after the last motion was detected the unit shall revert to night setback.

In the occupied mode the Vertical Unit Ventilator variable speed supply fan shall operate at its minimum motor speed setpoint defined by a predetermined adjustable value (30 - 50% maximum motor speed) or by the requirements of a space “air quality” CO^ sensor.

In this mode the master heating valve of the Vertical Unit Ventilator shall be modulated to maintain the space occupied heating setpoint (7O’F adjustable). The space temperature controller shall have a dead band between heating and cooling modes of 6’F - (adjustable set points).

The outdoor air damper shall be held at a minimum position as determined by the space “air quality” CO^ sensor. The supply fan shall operate continuously and shall ramp up from its minimum motor speed to its maximum motor speed in relation to the space heating requirements and the space “air quality” CO^ sensor.

A mixed air sensor setpoint of 3O’F (Adjustable) shall limit the outside air damper from opening above its setpoint value. Operation below this value shall annunciate an alarm condition and close the outside air damper to its minimum position.

The slave fan coil units shall be indexed on when the space heating requirements cannot be satisfied by the Vertical Unit Ventilator. The space temperature controller shall index the slave units on when the master heating valve is fully open and the space occupied heating setpoint (7O’F adjustable) drops below its setpoint value.

CITY_21MC100_012173076

NYC-WTC_000276231

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000276231Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000106411 · Box DEP Box 37

Union memorandum regarding environmental monitoring and cleanup protocols following the closure of Stuyvesant High School after the September 11 attacks.

Similar indexed content

NYC-WTC_000149798 · Box DEP Box 10

Generic form or header page from the Department of Environmental Protection regarding general World Trade Center notices and requests.

Similar indexed content

Compare copies and versions →