The advantage of the four pipe system vs. the two pipe system is that heating and cooling can be provided at the same time to different zones of the building due to their unique heating and cooling loads during intermediate seasons.

The two pipe system, however, is more prevalent since it is more cost effective and the simultaneous use of heating and cooling has been less prevalent as an energy reduction measure. Application of the two pipe system requires the building operator to be more conscience of the building heating and cooling loads and its response to variations in outside air temperature variations.

Major system disadvantages include:

• Limited filtration due to fractional motor horsepower and filter tracks width • Potential freeze protection due to piping and coil exposure to ambient outside air conditions.^ • Increased number of units to be maintained compared to central systems

Filtration Program

The filtration program required for the BOE unit ventilators included the following:

School# Unit Ventilators Stuyvesant High School 300 IS/PS 89 100 PS234 4 PS 150 Tribeca Learning Center Pk-5 12

Preliminary investigation indicated that upgrading the unit ventilators to meet the desired indoor air quality criteria, without extensive system modifications, would be difficult due to the limited system static capability and filter track provided by the existing units.

The existing units were provided with fractional horsepower motors (1/8 to ’A HP) that provided approximately 700 to 1000 cfm of supply air based on their system design. The filtration provided was limited to a 1” wide filter rack using disposable fiberglass filer media with a MERV rating of 1. The existing filters were functioning as protection for the systems coils with no consideration of indoor air quality.

The main objective of the unit ventilator filter upgrade program was to investigate several design options that would increase the efficiency of the unit ventilator systems to meet the design criteria.

8 This limitation is normally conntered by the use of ethylene glycol in the heating/cooling water.

DOE00048139.DOC Appendix 1 - Page 16

CITY_21MC100_011284787

NYC-WTC_000453563

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000453563Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →