Appendix 1 Application of Vertical Unit Ventilators

A 1.1 Description of Existing HVAC Systems - Stuyvesant High School

The Stuyvesant High School heating, ventilating, and air conditioning (HVAC) systems consist of central air handlers as scheduled in Table 1 and Unit Ventilators as summarized in Table 2. The central air handlers serve HVAC for the school corridors, gymnasium, auditorium, and other specialized use areas of the building as shown in Table 1.

Unit ventilators are provided for HVAC the school’s classrooms and offices in both the horizontal ceiling mounted types (Types E, F, G, H) and floor mounted cabinet types (A, B, C, D, I, J, K, The horizontal ceiling mounted unit ventilators are generally used to condition exterior and interior offices and to supplement floor mounted cabinet unit ventilators in specialized classrooms such as labs, shops, and computer rooms. The horizontal ceiling mounted unit ventilators are provided with ductwork and ceiling diffusers. The floor mounted cabinet type unit ventilators are generally used to condition exterior classrooms and are not provided with ductwork or ceiling diffusers. Outside air is provided via grilles in the outside wall and supply air is provided from a top mounted grille directly on the unit ventilator.

Description of Classroom HVAC and Smoke Purge Systems

The school’s classrooms are generally 690 to 730 square feet in area and are provided with two (2) floor mounted cabinet type unit ventilators that range in capacity from 1,000 to 1,250 cfm per unit. Larger shops and labs are typically provided with either three- (3) cabinet type unit ventilators or a combination of floor mounted and ceiling mounted ducted unit ventilators. The total unit ventilator supply air and minimum outside air for each classroom/lab obtained from the original Cooper Robertson & Partners Architects design drawings dated June 1989.

The minimum outside air from the classrooms (about 525 to 750 cfm) is exhausted out of the building via general exhaust fans GE-1 and GE-2, exhaust ductwork is provided from each classroom to the general exhaust duct risers.

The two existing corridor units HVAC 1 and 2 provide supply air to the school’s corridors. The supply air is returned via return air duct risers to return fans serving the HVAC-1 and HVAC-2 systems.

The air riser diagram for the school indicates a SI supply riser from the HVAC-1 supply unit and a R1 return riser. Similarly HVAC-2 supply’s air via the S2 riser and provided with a R2 return riser. Return air to the RI and R2 riser, from each classroom, is via the corridor ceiling return plenum. There is no return air ductwork provided for these

See Table 3

A:\6_R8trofmingHVAC_R.Ces«>r».d<x: Page AI-1

CITY_21MC100_010274204

NYC-WTC_000278817

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000278817Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →