Supply air requirement of 1500 cfm depending on classroom size. Outside air heating capability of 50% to 100% of design cfm Filtering: 2” OdorGuard III pre-filter and 12” cartridge after filter (95% efficiency at 1 micron) Variable speed fan motor with sufficient design static for the two system filters and supply cfm directly related to room temperature requirements. Demand ventilation control based on room CO levels. Economizer control capability (100% outside air free cooling) Barometric relief damper to insure proper room pressurization LonMark controls system for future DDC interface

Typical Large Lab/Shop (1200 to 2000+ SF) The existing HVAC system consist of two or three floor mounted unit ventilators and a horizontal ceiling mounted unit ventilator with ductwork and ceiling diffusers, Outside air requirements vary up to 1500 cfm depending on exhaust requirements for fume hoods, shop equipment, computers, etc. The retrofit program consist of the following: Conversion of the horizontal ceiling mounted unit ventilator to a vertical fan coil unit and interfacing to the existing ductwork. Conversion of the remaining floor mounted unit ventilators to fan coil units and the elimination of the introduction of outside air by these units. The new vertical unit ventilator will be interfaced to the existing ductwork and will have the following characteristics. Combination Hydronic Heating coil and Chilled water coil Supply air requirement of 1500 cfm depending on classroom size. Outside air heating capability of 100% of design cfm Filtering: 2” OdorGuard III pre-filter and 12” cartridge after filter (95% efficiency at 1 micron) Variable speed fan motor with sufficient design static for the two system filters and supply cfm directly related to room temperature requirements. Draw through system Demand ventilation control based on room CO levels. Economizer control capability (100% outside air free cooling) Barometric relief damper to insure proper room pressurization. LonMark controls system for future DDC interface

DOE00048139.DOC Appendix 1 - Page 24

CITY_21MC100_011284795

NYC-WTC_000453571

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000453571Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →