Asbestos Abatement

4. The supply air fan and the supply air damper for the active positive- pressurized duct shall be placed in the manual "on" positions to prevent shutdown by fail-safe mechanisms;

5. The return air fan and the return air dampers shall be shut down and locked-out;

6. All the seams of the HVAC dusts that pass through the Work Area shall be sealed;

1. The HVAC ducts that pass through the Work Area shall be covered with two (2) layers of 6-mil polyethylene sheeting, and all seams and edges of both layers shall be sealed airtight;

8. The supply air fans, return air fans, and all dampers servicing the Work Area itself shall be shut down and locked-out. All openings within the Work Area of supply and return air ducts shall be sealed with 3/8-inch plywood and two layers of 6-mil polyethylene;

9. When abatement occurs during periods while the HVAC system is shut down so that an alternative method of pressurization of the duct passing through the Work Area is used (e.g., by low-pressure "blowers", etc., directly coupled into the duct). Item #4 above shall be deleted and shall be replaced by the requirement to set the dampers of the HVAC duct in the manual closed positions, in order to effect pressurization.

C. Contractor to coordinate this item with the Facility and Resident Engineer at the commencement of work.

D. Where present HVAC systems (ducts) service a area, and that air system cannot be shut down, Contractor shall isolate and seal the ducts, both supply and return, at the boundary of that zone.

1. To isolate, cap, or seal a duct, the Contractor shall remove insulation from duct (if necessary), then disconnect linkage to fold shut all fire dampers. Contractor shall seal all edges and seams with caulk and duct-tape.

2. Contractor shall then cut existing duct and fold metal in and secure with approved fasteners. Contractor shall caulk and duct-tape all seams and edges.

3. All ducts shall then be completely wrapped and sealed with duct-tape and three (3) layers of reinforced polyethylene sheeting.

4. All ducts shall be restored to original working order at the end of the project. CAPITAL PROJECT NUMBER PO79201K 02081-62 100: CONTRACT DOCUMENTS REV. May 3,2000 - 62 -100% CONTRACT DOCUMENTS REV. 0: DATE

CITY_21MC100_006631311

NYC-WTC_000416823

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000416823Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Asbestos sampling chain of custody form

NYC-WTC_000233286

Chain of custody form for asbestos samples referencing New York State Department of Labor regulations and sample tracking details.

Similar indexed content

Asbestos, NY DOL reference

NYC-WTC_000441450

Asbestos standards reference page from NY Department of Labor materials.

Similar indexed content

Compare copies and versions →