Mr. Bernard P. Orlan October 15, 2001 Indoor Air Quality Assessment Page 4 Manhattan Acad, of Technology (d). P.S. 2M ATC Project No. 15-19125-0273
Jlelative Humidity
The relative humidity indoors ranged from 33.4 percent to 54.7 percent. All of the indoor measurements were within ASHICAE’s recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity was 45.3 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 580 ppm to 3,054 ppm. Six (6) CO2 measurements were above the .ASHRAE Standard 62-1999 recommended maxirnum concentration of <700 ppm above the background level. The outdoor (background) COo concentration was 426 ppm. Therefore, the acceptable level of CO2 at this location was 1,126 ppm (background level A 700 ppm). Two rooms (Rooms 307 & 308) had COg levels that were between 1.8 and 2.7 times greater than the recommended maximum. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary' source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 2 to 10 ppm. Six (6) of the indoor readings were at 50% or more of the NPAAQS/ASHRAE guideline of 9 ppm. One reading (Staircase Exit 4 & 5) was 10 ppm. The outdoor CO concentration was 2 ppm.
Respirable Particulates
Re.spirable particulate concentrations indoors ranged between 29 pg/m^ and 84 pg/m^. Twelve (12) of the sixteen (16) indoor measurements were above the NPA.AQS/ASHRAE guideline of 50 pg/m^ (annua’i average concentration of particulate matter 10 micrometers or less m aerodynamic diameter). The outdoor respirable paniculate concenfration was 98 pg/mA The high outdoor level is the major factor in the elevated indoor levels.
Tl'OC Concentration
TVOC concentrations indoors were 0 ppm for al] readings. The AIHA guideline for non- industrial buildings is 1 ppm. The outdoor TVOC concentration was 0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following: • .An elevated CO level (10 ppm) was recorded in Staircase Exit 4 & 5; • The custodian ofP.S. 2M reported that all of the building’s boilers were off; • The exhaust system was operating dunng the assessment; • There was a smell of food throughout the 3’"^ floor, the kitchen for P.S. 2M is in the basement of the building; • The air conditioning was running in Room 311 and Room 301; • Windows were open in Rooms 303, 304, 306, 307, 309. 318, 320 and the Boys Toilet; • Windows were Closed in Room 305 and no students were in the room;
CITY_21MC100_003267167
NYC-WTC_000324131
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000329970
Report of IAQ assessment for Technology at PS 2M.
10 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000200217
Cover letter and report summary from ATC Associates regarding an indoor air quality assessment conducted at P.S. 2M in October 2001.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000329949
LIAQ report for IAQ assessment at P.S. 2M / NYC DOE.
10 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000311687
Indoor air quality assessment conducted on October 9, 2001 at Stuyvesant High School.
9 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000329843
IAQ assessment report for PS 130M school building.
9 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335364
ATC IAQ measurements collected February 8, 2002 for the referenced school.
9 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313339
ATC IAQ memo detailing measurements and scope of work at PS 89M.
9 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328327
ATC reports IAQ measurements at PS 89M, 201 Warren St., for May 2002 per BOE request.
9 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000313593
ATC measures temperature and basic IAQ parameters at PS 89M for BOE in May 2002.
9 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000226873
ATC Associates report on indoor air quality measurements collected at P.S. 89M on January 17, 2002.
9 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000400606
Indoor air quality measurements collected for BOE at PS 89M.
9 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000328266
Indoor air quality measurements collected at the referenced school for BOE.
9 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000329970
Report of IAQ assessment for Technology at PS 2M.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350569
Final indoor air quality report for PS 65Q Annex, Oct 2002.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350647
September 2002 letter transmitting IAQ measurements for PS 65 project.
Similarity score 0.989 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350615
ATC indoor air quality report for PS 65Q Annex, 9/25/2002.
Similarity score 0.987 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000207834
Report on indoor air quality measurements collected at P.S. 65Q in September 2002 to verify acceptable air conditions.
Similarity score 0.985 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000350416
Memo presenting IAQ measurements for PS 65Q at 103-22 99th St.
Similarity score 0.984 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000329970
Report of IAQ assessment for Technology at PS 2M.
Similar indexed content
NYC-WTC_000200217
Cover letter and report summary from ATC Associates regarding an indoor air quality assessment conducted at P.S. 2M in October 2001.
Similar indexed content
NYC-WTC_000329949
LIAQ report for IAQ assessment at P.S. 2M / NYC DOE.
Similar indexed content
Indoor air quality assessment conducted on October 9, 2001 at Stuyvesant High School.
Similar indexed content
NYC-WTC_000329843
IAQ assessment report for PS 130M school building.
Similar indexed content