Mr, Bernard P. Orlan October 3 2002 Indoor Air Quality Assessment Page 3 F. S- 650________________ ATC Project No. 15-19125-0334

RelaUve Humidity

The relative humidity indoors ranged from 48.3 percent to 66.2 percent. Forty 6fte (41) of the indoor measurements for relative humidity were above the ASHRAF-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 67.1 to 74.2 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 491 ppm to 1059 ppm. All of the indoor measurements were within the ASHRAE Standard 62-2001 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 524 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1224 ppm (background level + 700 ppm). The highest reading (1059 ppm) was recorded in Room 1 approximately at 11:20 A.M. with 31 occupants. Levels above the recoinmcndcd niaxnuum do not indicate a health risk, Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

CarbgnA^noxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm for all readings. These concentrations were within the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.

OBSERVATIONS

During this assessment, ATC noted the following;

• The building was occupied at the time of the asscsSrtient; ■ No unusual odors were detected.

FINDINGS

Based on the real-time meastirenients, the following findings arc presented;

1. Eighty-three (83) of the indoor temperature measurements wwe below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 5S-1992 during ihe mechanical cooling season (summertime conditions). 2. Forty-one (41) of the indoor measurements for relative humidity were above the ASHRAE- reconunended range of 30 to 60 percent for occupant comfort. 3. All Of the indoor CO2 mcasuranents were within the ASHRAE Standard 62-2001 recommended maximum concentration of <700 ppm above the background level. 4. Concentrations of CO were within applicable guidelines.

CITY_21MC1OO_OO3O16674 NYC-WTC_000350571

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000350571Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →